CHARGING PROCEDURES:

1. Determine outdoor unit factory charge from Tabular Data Sheet.

2. Determine indoor coil adjustment (if any) from Tabular Data Sheet.

3. Calculate the additional charge for refrigerant piping using this Tabular Data Sheet if line length is greater than 15 feet (4.6 m).

4. Total system charge = item 1 + item 2 + item 3.

5. The manifold gauge set is already installed on the unit for evacuation and charging. Use these gauges to initially charge the system using system pressures and 

subcooling. You will find the charging information printed on the bottom of the unit data tag. More charging information is available in the “Service Data Applica-
tion Guide”, available online. For subsequent annual maintenance visits the charge verification display can be used to quickly check overall system condition and 
the system charge without attaching a separate manifold gauge set or temperature sensors.

6. Permanently mark the unit data plate with the total amount of refrigerant in the system.

SYSTEM CHARGE FOR VARIOUS MATCHED SYSTEMS 

Outdoor Unit

YXV24B21S

YXV36B21S

YXV48B21S

YXV60B21S

Indoor Unit

 1

Additional Charge, oz

AVV25B

0

AVV37B

0

AVV37C

0

AVV49C

0

AVV49D

0

AVV61C

0

AVV61D

0

CM25B

0

CM37B

0

CM37C

0

CM49C

0

CM49D

0

CM61C

0

CM61D

0

 All of the combinations shown in the above System Charge table require Advanced Main Air Circulating Fan indoor product. "Coil Only" matches 
are not available for these systems.

FOOTNOTES:

1. Charge adders shown above do not indicate that coils are rated for every application. Refer to Performance Data Tables for actual performance for specified 

system matches. Obtain certified system ratings from 

www.ahridirectory.org

.

IMPORTANT

It is recommended before starting the system to connect the thermostat to Wi-Fi using a local network or portable hot-spot so the
thermostat and system receive the latest software updates to optimize system performance.

Summary of Contents for AFFINITY SERIES YXV24 THRU 60

Page 1: ...high quality appearance Charge Assurance A built in touch screen instantly dis plays the system overall condition including the system pressures and refrigerant charge without the need to attach addi...

Page 2: ...nty Limited lifetime compressor warranty when registered online within 90 days of installa tion Agency Listed Safety certified by CSA to UL 1995 CSA 22 2 Performance certified to ANSI AHRI Standard 21...

Page 3: ...2 Rows Deep 1 1 2 2 Fins Inch 22 22 18 18 Liquid Line Set OD Field Installed 3 8 3 8 3 8 3 8 Vapor Line Set OD Field Installed 3 3 4 3 4 7 8 7 8 Unit Charge Lbs Oz 4 7 8 7 6 14 9 15 1 Charge Per Foot...

Page 4: ...stem charge without attaching a separate manifold gauge set or temperature sensors 6 Permanently mark the unit data plate with the total amount of refrigerant in the system SYSTEM CHARGE FOR VARIOUS M...

Page 5: ...is reduced until an acceptable current level is reached When the system reaches an acceptable current level the compres sor and fan return to normal operating conditions Over Under Voltage Protection...

Page 6: ...ERATION During cooling operation the main outdoor control will receive a communicated demand signal along with the current space temperature and setpoint The control algorithm will then utilize these...

Page 7: ...s shall be provided for field control wiring connections Service valves shall be provided for field refrig erant line connections Units shall be factory leak checked run tested and shipped with a hold...

Page 8: ...ount with center brace under center of compressor NOTE Ensure adequate wall support CAUTION Special care must be taken to avoid recirculation of discharge air through condenser coil CAUTION Care must...

Page 9: ...ay be reduced to 18 minimum provided the service access clearance is increased to 24 minimum and the clearance on each remaining side is maintained at 18 minimum NOTE Clearance to one side of the unit...

Page 10: ...9 16 5 18 4 14 2 15 0 15 3 16 8 18 8 KW 1 35 1 34 1 34 1 31 1 27 1 37 1 36 1 37 1 34 1 30 1 40 1 39 1 40 1 37 1 33 85 T C 19 9 21 1 21 4 24 3 27 1 20 4 21 8 22 3 24 9 28 0 20 9 22 5 23 2 25 5 29 0 S C...

Page 11: ...24 3 26 5 21 1 21 9 22 6 24 9 26 9 KW 2 02 2 02 2 02 2 00 1 93 2 07 2 07 2 07 2 05 1 98 2 12 2 12 2 12 2 10 2 04 85 T C 29 9 31 3 32 4 35 7 40 0 30 8 32 3 33 8 37 7 41 7 31 7 33 3 35 1 39 8 43 4 S C...

Page 12: ...2 35 3 31 0 30 1 29 8 32 7 35 5 KW 2 70 2 69 2 69 2 68 2 65 2 76 2 76 2 77 2 75 2 73 2 83 2 83 2 84 2 82 2 80 85 T C 41 5 42 9 43 2 47 7 52 9 43 2 43 9 44 0 48 5 53 6 45 0 45 0 44 8 49 3 54 2 S C 28...

Page 13: ...41 5 45 1 37 6 38 4 38 5 42 2 45 5 KW 3 65 3 69 3 68 3 70 3 72 3 76 3 78 3 78 3 79 3 82 3 86 3 87 3 87 3 88 3 91 85 T C 51 3 53 9 54 7 59 8 65 5 53 2 55 2 55 7 60 8 66 5 55 1 56 5 56 7 61 8 67 5 S C 3...

Page 14: ...ct to change without notice Published in U S A 5331838 YTG A 0317 Copyright 2017 by Johnson Controls Inc All rights reserved Supersedes Nothing York International Corp 5005 York Drive Norman OK 73069...

Reviews: