Johnson Controls Unitary Products

PERFORMANCE DATA - 2 TON

Multipliers for determining the performance with other indoor sections.

NOTE: 

For dry bulb temperatures different than those listed (between 73-87 °

F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed 

temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.

NOTICE

Outdoor units must be applied with Johnson Controls Unitary Products indoor coils, so Condenser Only data is not provided.

COOLING PERFORMANCE DATA- HIGH

AIR CONDITIONER MODEL NO.

YXV24B21S

AIR TEMP.

ENTERING

OUTDOOR UNIT (°F)

IDCFM

680

780

880

ID DB (°F)

80

80

75

80

80

80

80

75

80

80

80

80

75

80

80

ID WB (°F)

57

62

62

67

72

57

62

62

67

72

57

62

62

67

72

55

T.C.

19.3

20.0

21.1

22.9

25.7

19.3

20.2

21.15

23.5

26.75

19.3

20.4

21.2

24.1

27.8

S.C.

13.4

14.1

14.3

15.7

17.7

13.45 14.25

14.4

16.05 18.15

13.5

14.4

14.5

16.4

18.6

KW

1.08

1.07

1.03

1.00

0.94

1.04

1.11

1.06

1.03

0.98

1.00

1.14

1.09

1.06

1.01

65

T.C.

19.5

20.4

21.2

23.4

26.4

19.6

20.7

21.6

24.0

27.2

19.8

21.1

22.1

24.6

28.1

S.C.

13.5

14.3

14.4

15.9

17.9

13.7

14.5

14.7

16.3

18.3

13.9

14.7

14.9

16.6

18.7

KW

1.21

1.20

1.18

1.16

1.11

1.20

1.24

1.21

1.18

1.14

1.20

1.27

1.25

1.21

1.17

75

T.C.

19.7

20.7

21.3

23.8

27.0

20.0

21.3

22.1

24.4

27.7

20.2

21.8

22.9

25.0

28.4

S.C.

13.6

14.4

14.5

16.1

18.0

13.9

14.7

14.9

16.5

18.4

14.2

15.0

15.3

16.8

18.8

KW

1.35

1.34

1.34

1.31

1.27

1.37

1.36

1.37

1.34

1.30

1.40

1.39

1.40

1.37

1.33

85

T.C.

19.9

21.1

21.4

24.3

27.1

20.4

21.8

22.3

24.9

28.0

20.9

22.5

23.2

25.5

29.0

S.C.

13.7

14.6

14.6

16.3

18.1

14.1

14.9

15.0

16.7

18.6

14.6

15.3

15.5

17.0

19.1

KW

1.62

1.61

1.61

1.60

1.57

1.65

1.64

1.65

1.63

1.60

1.68

1.68

1.68

1.66

1.63

95

T.C.

20.0

21.5

21.5

24.7

27.1

20.8

22.4

22.5

25.3

28.3

21.6

23.2

23.4

25.9

29.5

S.C.

13.8

14.7

14.7

16.5

18.1

14.4

15.2

15.2

16.9

18.7

14.9

15.6

15.6

17.2

19.3

KW

1.89

1.89

1.89

1.88

1.86

1.93

1.92

1.92

1.91

1.89

1.96

1.96

1.96

1.94

1.93

105

T.C.

20.2

21.9

21.6

25.2

27.2

21.2

22.9

22.6

25.8

28.6

22.3

23.9

23.7

26.4

30.1

S.C.

13.9

14.9

14.8

16.7

18.2

14.6

15.4

15.3

17.1

18.9

15.3

15.9

15.8

17.4

19.6

KW

2.39

2.39

2.39

2.38

2.37

2.43

2.42

2.42

2.41

2.41

2.47

2.46

2.45

2.45

2.44

115

T.C.

20.3

22.3

21.7

25.6

27.2

21.7

23.5

22.8

26.2

28.9

23.0

24.6

23.9

26.8

30.6

S.C.

14.0

15.0

14.9

16.9

18.2

14.8

15.6

15.4

17.3

19.0

15.6

16.2

15.9

17.6

19.8

KW

2.88

2.87

2.87

2.86

2.86

2.92

2.91

2.90

2.90

2.90

2.96

2.94

2.93

2.94

2.94

125

T.C.

20.5

22.7

21.8

26.1

27.3

22.1

24.0

23.0

26.7

29.2

23.7

25.3

24.2

27.3

31.2

S.C.

14.1

15.2

15.0

17.1

18.3

15.0

15.8

15.5

17.5

19.2

16.0

16.5

16.1

17.8

20.1

KW

3.36

3.35

3.35

3.35

3.36

3.41

3.39

3.38

3.39

3.40

3.45

3.43

3.42

3.43

3.44

NOTE: 

ALL CAPACITIES INCLUDE INDOOR FAN HEAT. KW VALUES ARE FOR THE SYSTEM (O INDOOR).

Green shaded cells are ACCA (TVA) conditions.

Blue shaded cells are AHRI conditions.

COIL MULTIPLIERS - 2 TON

Air Handler

Coil

T.C.

S.C.

KW

AVV25BE12

1.00

1.00

1.00

Summary of Contents for AFFINITY SERIES YXV24 THRU 60

Page 1: ...high quality appearance Charge Assurance A built in touch screen instantly dis plays the system overall condition including the system pressures and refrigerant charge without the need to attach addi...

Page 2: ...nty Limited lifetime compressor warranty when registered online within 90 days of installa tion Agency Listed Safety certified by CSA to UL 1995 CSA 22 2 Performance certified to ANSI AHRI Standard 21...

Page 3: ...2 Rows Deep 1 1 2 2 Fins Inch 22 22 18 18 Liquid Line Set OD Field Installed 3 8 3 8 3 8 3 8 Vapor Line Set OD Field Installed 3 3 4 3 4 7 8 7 8 Unit Charge Lbs Oz 4 7 8 7 6 14 9 15 1 Charge Per Foot...

Page 4: ...stem charge without attaching a separate manifold gauge set or temperature sensors 6 Permanently mark the unit data plate with the total amount of refrigerant in the system SYSTEM CHARGE FOR VARIOUS M...

Page 5: ...is reduced until an acceptable current level is reached When the system reaches an acceptable current level the compres sor and fan return to normal operating conditions Over Under Voltage Protection...

Page 6: ...ERATION During cooling operation the main outdoor control will receive a communicated demand signal along with the current space temperature and setpoint The control algorithm will then utilize these...

Page 7: ...s shall be provided for field control wiring connections Service valves shall be provided for field refrig erant line connections Units shall be factory leak checked run tested and shipped with a hold...

Page 8: ...ount with center brace under center of compressor NOTE Ensure adequate wall support CAUTION Special care must be taken to avoid recirculation of discharge air through condenser coil CAUTION Care must...

Page 9: ...ay be reduced to 18 minimum provided the service access clearance is increased to 24 minimum and the clearance on each remaining side is maintained at 18 minimum NOTE Clearance to one side of the unit...

Page 10: ...9 16 5 18 4 14 2 15 0 15 3 16 8 18 8 KW 1 35 1 34 1 34 1 31 1 27 1 37 1 36 1 37 1 34 1 30 1 40 1 39 1 40 1 37 1 33 85 T C 19 9 21 1 21 4 24 3 27 1 20 4 21 8 22 3 24 9 28 0 20 9 22 5 23 2 25 5 29 0 S C...

Page 11: ...24 3 26 5 21 1 21 9 22 6 24 9 26 9 KW 2 02 2 02 2 02 2 00 1 93 2 07 2 07 2 07 2 05 1 98 2 12 2 12 2 12 2 10 2 04 85 T C 29 9 31 3 32 4 35 7 40 0 30 8 32 3 33 8 37 7 41 7 31 7 33 3 35 1 39 8 43 4 S C...

Page 12: ...2 35 3 31 0 30 1 29 8 32 7 35 5 KW 2 70 2 69 2 69 2 68 2 65 2 76 2 76 2 77 2 75 2 73 2 83 2 83 2 84 2 82 2 80 85 T C 41 5 42 9 43 2 47 7 52 9 43 2 43 9 44 0 48 5 53 6 45 0 45 0 44 8 49 3 54 2 S C 28...

Page 13: ...41 5 45 1 37 6 38 4 38 5 42 2 45 5 KW 3 65 3 69 3 68 3 70 3 72 3 76 3 78 3 78 3 79 3 82 3 86 3 87 3 87 3 88 3 91 85 T C 51 3 53 9 54 7 59 8 65 5 53 2 55 2 55 7 60 8 66 5 55 1 56 5 56 7 61 8 67 5 S C 3...

Page 14: ...ct to change without notice Published in U S A 5331838 YTG A 0317 Copyright 2017 by Johnson Controls Inc All rights reserved Supersedes Nothing York International Corp 5005 York Drive Norman OK 73069...

Reviews: