MECHANICAL SPECIFICATIONS

MANUFACTURE AND CERTIFICATIONS

• Units shall be manufactured in an ISO 9001 certified facility.

• Units shall be certified by CSA to UL 1995 / CSA 22.2 and

performance certified to ANSI/AHRI Standard 210/240.

• Units shall be sound tested according to ANSI/AHRI Stan-

dard 270.

• Certified matched system ratings will be available for down-

load from the AHRI online directory at 

www.ahridirectory.org

.

• Unit packaging shall be marked, “Assembled in the USA”.

• Unit shall be labeled with the ENERGY STAR logo.

• Unit shall be recognized as ENERGY STAR Most Efficient.

(May apply only to select models in each series).

UNIT APPLICATION

• Units shall be approved for cooling operation between 35ºF

and 125ºF without modification.

• Units shall be approved for linesets up to 80 feet equivalent

length without modification.

• Units shall be approved for installation within 6 inches of a

flat vertical wall without modification, according to the
instructions in the technical literature.

• Units shall be certified to the 5th Edition (2014) of the Florida

Building Code for both Ground Mounted and Rooftop
Mounted applications up to 200 feet above grade with
approved mounting kit.

UNIT ACCESS

• Units shall have a removable fan guard that can be removed

independently of the top for interior access through the top of
the unit without damaging the coil.

• Units shall have two removable stamped steel coil guards for

exterior coil access.

• Units shall have a separate compartment for electrical con-

trols that can be accessed without disturbing the unit airflow.

• Units shall have a blockoff panel that can be removed to pro-

vide interior unit access through the side of the unit.

• Units shall have a removable blockoff panel and a swing

away removable electrical panel that provides sufficient inte-
rior unit access for removing the compressor through the
side of the unit.

UNIT CONSTRUCTION

• Units shall be shipped completely wired, piped and assem-

bled. Wiring pigtails shall be provided for field control wiring
connections. Service valves shall be provided for field refrig-
erant line connections.

• Units shall be factory leak checked, run tested, and shipped

with a holding charge of R-410A refrigerant.

• Unit cabinet components shall be G90 equivalent steel fin-

ished with powder-coat paint rated at a minimum of 1,000
hours under ASTM B117 testing.

• Unit shall be constructed with a composite base pan to pre-

vent corrosion and minimize noise and vibration.

• Units shall have a single corner post opposite the electrical

control box and two independently removable steel coil
guard panels to optimize cabinet strength and serviceability.

• Units shall have L-shaped stamped sheet metal coil guards

with extruded louvers for maximum panel durability and sys-
tem protection.

• Units shall have a factory installed filter-drier for faster instal-

lation and improved system reliability.

• Unit base valves shall be mounted diagonally on the unit

base pan with service ports that provide sufficient clearance
for low-loss hose fittings.

• Units shall be constructed with a high pressure switch and a

low pressure for system protection.

• Units shall be constructed with all badging and labels applied

at the factory.

UNIT COMPONENTS

• Compressor shall be hermetic with internal electrical over-

load protection and internal overpressure protection.

• Compressor shall be mounted on rubber vibration isolators

that do not require the removal of transportation clips or
brackets.

• Units shall be constructed using a scroll compressor paired

with an inverter drive.

• Condenser fan shall be direct drive with vertical air discharge

for low sound levels.

• Condenser fan blades shall be swept-wing to minimize

sound.

• Condenser fan motor shall be ECM construction with perma-

nently lubricated ball bearing motors approved for vertical
shaft applications.

• Condenser coil shall be air cooled and constructed of

enhanced aluminum fins mechanically bonded to internally
enhanced Ø 7mm copper tubing.

UNIT WARRANTIES

• Unit manufacturer shall provide a Limited Lifetime compres-

sor warranty with unit registration.

• Unit manufacturer shall provide a limited 5-Year parts war-

ranty extended to 10 years with registration.

Summary of Contents for AFFINITY SERIES YXV24 THRU 60

Page 1: ...high quality appearance Charge Assurance A built in touch screen instantly dis plays the system overall condition including the system pressures and refrigerant charge without the need to attach addi...

Page 2: ...nty Limited lifetime compressor warranty when registered online within 90 days of installa tion Agency Listed Safety certified by CSA to UL 1995 CSA 22 2 Performance certified to ANSI AHRI Standard 21...

Page 3: ...2 Rows Deep 1 1 2 2 Fins Inch 22 22 18 18 Liquid Line Set OD Field Installed 3 8 3 8 3 8 3 8 Vapor Line Set OD Field Installed 3 3 4 3 4 7 8 7 8 Unit Charge Lbs Oz 4 7 8 7 6 14 9 15 1 Charge Per Foot...

Page 4: ...stem charge without attaching a separate manifold gauge set or temperature sensors 6 Permanently mark the unit data plate with the total amount of refrigerant in the system SYSTEM CHARGE FOR VARIOUS M...

Page 5: ...is reduced until an acceptable current level is reached When the system reaches an acceptable current level the compres sor and fan return to normal operating conditions Over Under Voltage Protection...

Page 6: ...ERATION During cooling operation the main outdoor control will receive a communicated demand signal along with the current space temperature and setpoint The control algorithm will then utilize these...

Page 7: ...s shall be provided for field control wiring connections Service valves shall be provided for field refrig erant line connections Units shall be factory leak checked run tested and shipped with a hold...

Page 8: ...ount with center brace under center of compressor NOTE Ensure adequate wall support CAUTION Special care must be taken to avoid recirculation of discharge air through condenser coil CAUTION Care must...

Page 9: ...ay be reduced to 18 minimum provided the service access clearance is increased to 24 minimum and the clearance on each remaining side is maintained at 18 minimum NOTE Clearance to one side of the unit...

Page 10: ...9 16 5 18 4 14 2 15 0 15 3 16 8 18 8 KW 1 35 1 34 1 34 1 31 1 27 1 37 1 36 1 37 1 34 1 30 1 40 1 39 1 40 1 37 1 33 85 T C 19 9 21 1 21 4 24 3 27 1 20 4 21 8 22 3 24 9 28 0 20 9 22 5 23 2 25 5 29 0 S C...

Page 11: ...24 3 26 5 21 1 21 9 22 6 24 9 26 9 KW 2 02 2 02 2 02 2 00 1 93 2 07 2 07 2 07 2 05 1 98 2 12 2 12 2 12 2 10 2 04 85 T C 29 9 31 3 32 4 35 7 40 0 30 8 32 3 33 8 37 7 41 7 31 7 33 3 35 1 39 8 43 4 S C...

Page 12: ...2 35 3 31 0 30 1 29 8 32 7 35 5 KW 2 70 2 69 2 69 2 68 2 65 2 76 2 76 2 77 2 75 2 73 2 83 2 83 2 84 2 82 2 80 85 T C 41 5 42 9 43 2 47 7 52 9 43 2 43 9 44 0 48 5 53 6 45 0 45 0 44 8 49 3 54 2 S C 28...

Page 13: ...41 5 45 1 37 6 38 4 38 5 42 2 45 5 KW 3 65 3 69 3 68 3 70 3 72 3 76 3 78 3 78 3 79 3 82 3 86 3 87 3 87 3 88 3 91 85 T C 51 3 53 9 54 7 59 8 65 5 53 2 55 2 55 7 60 8 66 5 55 1 56 5 56 7 61 8 67 5 S C 3...

Page 14: ...ct to change without notice Published in U S A 5331838 YTG A 0317 Copyright 2017 by Johnson Controls Inc All rights reserved Supersedes Nothing York International Corp 5005 York Drive Norman OK 73069...

Reviews: