SECTION V: COIL METERING DEVICES

A piston or a TXV is to be installed in the field. There is an installation

manual that comes with the TXV kit. It is recommended to install the
piston or TXV kit prior to installation of coil and brazing of line set. Until
brazing is completed and cooled, the TXV sensing bulb must not be
installed.

The outdoor technical guide for outdoor units should be consulted for
required piston or TXV on the indoor coil. The piston and the Schrader
core are supplied with the outdoor unit. When the piston is used instead
of the TXV, the Schrader core is installed in the suction line equalizer
connection port and is capped with the supplied plastic cap. The
Schrader core must not be installed if the TXV is installed, because the
TXV equalizer line attaches to the equalizer connection port. 

PISTON INSTALLATION

Install Schrader Valve Core and 

Piston

 as follows:

1.

After holding charge is completely discharged, remove black plas-

tic cap from equalizer connection port on the vertical part of the
vapor line. 

2.

Distributor position must be adjusted to allow the preformed liquid
line assembly to properly line up with the hole in the tubing access
panel. Raise the distributor body approximately 2” toward the top of
the coil or what would be the top of the coil if coil was in the upflow
position. See Figure 9. Adjust as necessary.

3.

Install Schrader valve core supplied with the outdoor unit into the
equalizer fitting connection port using a valve core tool.

4.

Loosen and remove the liquid line connection nut and the sealing
disc from the distributor assembly. Note that the fitting has right
hand threads.

5.

Slide the nut over the liquid line to be installed, and discard the
seal disc.

6.

Install required size piston into the distributor. Refer to supplied
Tabular Data Sheet for specific piston size and indoor coil match
up. See Figure 10.

7.

Verify that the Teflon washer is still in place in the distributor open-
ing. See Figure 10.

8.

After piston is installed, install the liquid line to the top of the pis-

ton/distributor assembly. Hand tighten, and turn an additional 1/4
turn to seal. Do not over tighten fittings.

9.

Replace black plastic cap on unused equalizer fitting connection
port.

10. After line set is installed, leak test the system.

THERMOSTATIC EXPANSION VALVE (TXV) INSTAL-

LATION

The following are basic steps for installation. For detailed instructions, 
refer to the Installation Instructions accompanying the TXV kit. Install 
TXV kit as follows:

1.

Relieve the holding charge by depressing Schrader core on the
suction manifold stub out.

2. After holding charge is completely discharged, loosen and remove

the Schrader core.

 CAUTION

COIL UNDER PRESSURE.
Verify that pressure has been released by depressing schrader valve
core shown in Figure 2. 
The coil requires a metering device to be added. 
See outdoor unit documentation for correct TXV or piston to be used.

NOTICE

To prevent moisture and contaminates from entering the system, the
coil should not be open to atmosphere for extended periods of time. If
the coil cannot be brazed into the refrigeration system during a rou-
tine installation period, the ends should be temporarily closed or
plugged. For a short term delay, use masking tape over the ends of
the copper tubing to close the tube from the air. For a longer term
delay, use plugs or caps. There is no need to purge the coil if this pro-
cedure is followed.

 WARNING

Failure to install Schrader Valve Core in the vapor line 

equalizer con-

nection port

 for piston applications could result in total refrigerant loss

of the system!

!

!

 FIGURE 9:  

Recommended Distributor Adjustment

 FIGURE 10:  

Piston Installation

 CAUTION

Do not overtorque. Do not use slip joint pliers. This will distort the alu-
minum distributor and the brass fitting (potentially causing leaks).

 CAUTION

Outdoor unit model numbers ending with an “H” have a factory
installed hard start kit which is required when a TXV is installed. Out-
door unit model numbers with no “H” ending do not require a hard
start kit unless local regulations dictate it.

IMPORTANT

Refer to the Technical Guide for the unit to determine the proper TXV
kit to be used on this product.

$

A

0

3

0

5-

001

DI

S

TRIBUT

O

R

PI

S

T

O

N

LI

Q

UID LINE 

S

WIVEL

CO

UPLING

(Th

is

tting

 

is

 

a

 

rig

h

t

-h

anded

 

t

h

read

.

T

urn

 co

unter

-clockw

ise

 

t

rem

ov

e

.)

TEFL

O

N WA

S

HER

!

!

Summary of Contents for AE SERIES

Page 1: ...nit may be used for upflow downflow horizontal right or horizontal left applications These units may be located in a closet utility room attic crawl space or basement These versatile models may be use...

Page 2: ...ons must be observed as applicable 12 These instructions cover minimum requirements and conform to existing national standards and safety codes In some instances these instructions exceed certain loca...

Page 3: ...ting any wiring duct work or piping FIGURE 2 Pressure Check A0271 001 DEPRESS SCHRADER CORE TO CHECK FOR PRESSURE ONE TIME NOTE Verify that the coil is under pressure when received FIGURE 3 Dimensions...

Page 4: ...allowing condensate to drain away from structure 5 When an indoor coil is installed in an attic or above a finished ceil ing an auxiliary drain pan should be provided under the air handler as is spec...

Page 5: ...short or where sound may be a problem acoustical duct liner should be used inside the duct Use flexible duct connectors to minimize the transmission of vibration noise into the conditioned space Insu...

Page 6: ...m be attached to the supply opening Refer to Figure 8 as a visual aid The use of this block off plate will enable better air circulation across the limit switches AIR FILTERS Return air filters are re...

Page 7: ...top of the pis ton distributor assembly Hand tighten and turn an additional 1 4 turn to seal Do not over tighten fittings 9 Replace black plastic cap on unused equalizer fitting connection port 10 Af...

Page 8: ...k position b If bulb installation is made on a vertical run ensure that the bulb is a minimum of 8 inches 20 3 cm away from elbow coming out of the coil Position the bulb with the tail of the bulb at...

Page 9: ...isolated by using appropriate hangers or strapping SECTION VII CONDENSATE DRAIN CONNECTIONS All drain lines should be trapped a minimum of three inches should be pitched away from unit drain pan and...

Page 10: ...uit should be terminated at the electrical control box To determine proper wire sizing refer to Tables 6 10 and the latest edition of the National Electric Code or in Canada the Canadian electrical Co...

Page 11: ...ppropriate speed tap according to Table 4 If electric heat requires speed tap 5 the highest speed tap available for cooling heat pump heating is tap 4 If a lower circulating speed is desired for fan o...

Page 12: ...Requirement For a power distribution voltage that is different than the provided nominal voltage multiply the kW and MBH data from the table by the conversion factor in the following table DISTRIBUTI...

Page 13: ...6 45 45 6HK 0 1 6501006 40 49 3 53 8 50 60 6HK 1 2 6501306 52 62 5 68 5 70 70 6HK 1 2 6501506 60 70 9 77 7 80 80 6HK 1 2 6501806 72 84 1 92 4 90 100 6HK 1 2 6502006 80 92 5 101 7 100 110 36C 6HK 0 1...

Page 14: ...20 25 6HK 0 1 6500506 20 30 1 32 4 35 35 6HK 0 1 6500806 32 43 4 47 1 45 50 6HK 0 1 6501006 40 51 8 56 3 60 60 6HK 1 2 6501306 52 65 0 71 0 70 80 6HK 1 2 6501506 60 73 4 80 2 80 90 6HK 1 2 6501806 72...

Page 15: ...9 50 45 60 50 48C 6HK16501306 52 27 3 37 6 29 3 41 5 30 40 30 45 6HK16501506 60 30 2 43 3 32 5 47 9 35 45 35 50 6HK16501806 72 47 5 39 0 51 6 43 1 50 40 60 45 6HK16502006 80 51 8 43 3 56 4 47 9 50 45...

Page 16: ...6501025 23 1 28 3 30 9 30 35 6HK36501525 34 6 40 7 44 7 45 45 36B 6HK36501025 23 1 29 8 32 4 30 35 6HK36501525 34 6 42 2 46 2 45 50 6HK36501825 41 6 49 8 54 6 50 55 6HK46502025 46 2 54 8 60 1 55 70 36...

Page 17: ...l Code and local codes to determine correct wire sizing TABLE 11 Air Flow Data CFM 1 Models Blower Motor Speed External Static Pressure in wc 0 10 0 20 0 30 0 40 0 50 0 60 0 70 18B 5 HI 1132 1107 1074...

Page 18: ...ether to determine the total external system static pressure If a filter rack is installed on the return air end of the air handler or indoor coil sec tion make sure to measure the return air duct sta...

Page 19: ...nit Technical Guide Is the TXV bulb positioned correctly Is temperature bulb insulated Is equalizer line connected 3 MINIMUM HANDMADE TRAP PREMADE TRAPS SECONDARY PRIMARY WERE THE PRIMARY AND SECONDAR...

Page 20: ...AND NATIONAL CODES MUST BE FOLLOWED SEE INSTALLATION INSTRUCTIONS FOR PROPER LOW VOLTAGE FIELD WIRING CONNECTIONS LEGEND LS LIMIT SWITCH SEQ SEQUENCER HE HEATING ELEMENT FL FUSIBLE LINK H SEQUENCER H...

Page 21: ...N BLUE BLUE BLUE BLUE YELLOW YELLOW BLACK BLACK YELLOW YELLOW BLACK BLACK RED WHITE BLACK BLUE BLACK BLUE YELLOW BLACK YELLOW YELLOW BLUE BLACK BLUE BLACK YELLOW RLY 1 RLY 2 RLY 3 RLY 6 RLY 5 RLY 4 HE...

Page 22: ...6 22 Johnson Controls Unitary Products SECTION XVII TYPICAL THERMOSTAT CONNECTIONS FIGURE 23 Typical Thermostat Wiring Diagram ECM A0370 002 W2 X L X L X L X L FIELD INSTALLED JUMPER IF SINGLE STAGE T...

Page 23: ...dry bulb temperature Return air dry bulb temperature Temperature drop 1 2 3 4 5 Low Medium Low Medium Medium High High A B C D Outside air dry bulb temperature Return air wet bulb temperature Supply...

Page 24: ...oting and correcting any problems Operate the unit through cooling cycles from the thermostat noting and correcting any problems Operate the unit through mechanical heating cycles from the thermostat...

Reviews: