background image

5169032-UIM-C-0416

4

Johnson Controls Unitary Products

SECTION III: UNIT INSTALLATION

UNIT SIZING

1.

The size of the unit should be based on an acceptable heat loss or
gain calculation for the structure. The ACCA – Manual J or other
approved methods may be used. Reference Figure 3 and Table 1.

2.

Only connect the air handler to a duct system which has an external
static pressure within the allowable range. 

3. Airflow must be within the minimum and maximum limits approved

for electric heat, indoor coils and outdoor units.

4.

When an air handler is installed so that supply ducts carry air circu-
lated by the air handler to areas outside the space containing the
air handler, the return air shall also be handled by duct(s) sealed to
the air handler casing and terminating in the space to be cooled/
heated. 

5.

Refer to the unit rating plate for the air handler model number, and
then see the dimensions page of this instruction for supply air ple-
num dimensions. The plenum must be installed according to the
instructions. 

6.

The installer must check available supply power and verify that it is
within the normal operating voltage range for the unit. The accept-
able voltage range for these units is as follows:

CLEARANCES 

Clearances must be taken into consideration, and provided for as
follows:

1.

Refrigerant piping and connections - minimum 12” recommended.

2.

Maintenance and servicing access - minimum 36” from front of unit
recommended for blower motor / coil replacement.

3.

Condensate drain lines routed to clear filter and panel access.

4.

Filter removal - minimum 36” recommended.

5.

The duct work connected to this unit is designed for zero clearance
to combustible materials.

6. A combustible floor base accessory is available for downflow appli-

cations of this unit, if required by local code.

LOCATION

Location is usually predetermined. Check with owner’s or dealer’s
installation plans. If location has not been decided, consider the
following in choosing a suitable location:

1.

Select a location with adequate structural support, space for service
access, and clearance for air return and supply duct connections.

2.

Using hanging brackets to wall mount this single piece air handler
unit is not recommended.

3.

Normal operating sound levels may be objectionable if the air han-
dler is placed directly over some rooms such as bedrooms, study,
etc.

4.

Select a location that will permit installation of condensate line to an
open drain or outdoors allowing condensate to drain away from
structure.

5.

When an indoor coil is installed in an attic or above a finished ceil-
ing, an auxiliary drain pan should be provided under the air handler
as is specified by most local building codes.

6.

Proper electrical supply must be available.

7.

If unit is located in an area of high humidity (i.e. an unconditioned
garage or attic), nuisance sweating of casing may occur. On these
installations, unit duct connections and other openings should be
properly sealed, and a wrap of 2” fiberglass insulation with vinyl
vapor barrier should be used.

AIR HANDLER CONFIGURATION

These air handler units are supplied ready to be installed in an upflow
or horizontal left position. Refer to Figure 4. If the unit requires either
downflow or horizontal right airflow configurations, the unit must have
the coil assembly repositioned. Refer the Downflow or Horizontal Right
Conversion procedures.

 

DOWNFLOW OR HORIZONTAL RIGHT CONVERSION

1.

Remove coil access panel.

2.

Slide coil/drain pan assembly out of air handler.

3.

Note the lettered position of the center support bar for the coil/drain
pan. Remove the center support bar by sliding the forward end of
the support bar to the right or left until the lower finger clears the
structure. 

NOTICE

Avoid handling aluminum coil components after handling the copper 

line set or other tubing without first cleaning hands.

Entering Air Temperature Limits

Wet Bulb Temp.°F

Dry Bulb Temp. °F

Min.

Max.

Min.

Max.

57

72

65

95

Air Handler Voltage

Normal Operating 

1

 Voltage Range

1. Rated in accordance with ARI Standard 110, utilization range “A”.

208V-230V-1-60

187V-253V

NOTICE

The primary and secondary drain line must be trapped to allow proper
drainage of condensate water. The secondary drain line should be
piped to a location that will give the occupant a visual warning that the
primary drain is clogged. If the secondary drain line is not used, it
must be capped.

 FIGURE 4:  

Typical Installation

NOTICE

Convert air handler to correct orientation prior to installation. Conver-
sion must be made before brazing the refrigerant connections to the
coil.

NOTICE

The center support bar for the coil/drain pan has a position identifier
embossed into the cabinet structure between the two forward fingers
of the support bar. There are four position identifiers: A, B, C, or D.
The lettered hole location can differ from unit to unit due to the cabi-
net width of the air handler. After removal and reinstallation, the cen-
ter support bar must be installed in the same lettered position that it
was originally.

UPFL

O

W

H

O

RIZ

O

NTAL RIGHT

H

O

RIZ

O

NTAL LEFT

HEAT

HEA

T

HEA

T

D

O

WNFL

O

W

HEAT

A

0

33

0

-

001

Summary of Contents for AE SERIES

Page 1: ...nit may be used for upflow downflow horizontal right or horizontal left applications These units may be located in a closet utility room attic crawl space or basement These versatile models may be use...

Page 2: ...ons must be observed as applicable 12 These instructions cover minimum requirements and conform to existing national standards and safety codes In some instances these instructions exceed certain loca...

Page 3: ...ting any wiring duct work or piping FIGURE 2 Pressure Check A0271 001 DEPRESS SCHRADER CORE TO CHECK FOR PRESSURE ONE TIME NOTE Verify that the coil is under pressure when received FIGURE 3 Dimensions...

Page 4: ...allowing condensate to drain away from structure 5 When an indoor coil is installed in an attic or above a finished ceil ing an auxiliary drain pan should be provided under the air handler as is spec...

Page 5: ...short or where sound may be a problem acoustical duct liner should be used inside the duct Use flexible duct connectors to minimize the transmission of vibration noise into the conditioned space Insu...

Page 6: ...m be attached to the supply opening Refer to Figure 8 as a visual aid The use of this block off plate will enable better air circulation across the limit switches AIR FILTERS Return air filters are re...

Page 7: ...top of the pis ton distributor assembly Hand tighten and turn an additional 1 4 turn to seal Do not over tighten fittings 9 Replace black plastic cap on unused equalizer fitting connection port 10 Af...

Page 8: ...k position b If bulb installation is made on a vertical run ensure that the bulb is a minimum of 8 inches 20 3 cm away from elbow coming out of the coil Position the bulb with the tail of the bulb at...

Page 9: ...isolated by using appropriate hangers or strapping SECTION VII CONDENSATE DRAIN CONNECTIONS All drain lines should be trapped a minimum of three inches should be pitched away from unit drain pan and...

Page 10: ...uit should be terminated at the electrical control box To determine proper wire sizing refer to Tables 6 10 and the latest edition of the National Electric Code or in Canada the Canadian electrical Co...

Page 11: ...ppropriate speed tap according to Table 4 If electric heat requires speed tap 5 the highest speed tap available for cooling heat pump heating is tap 4 If a lower circulating speed is desired for fan o...

Page 12: ...Requirement For a power distribution voltage that is different than the provided nominal voltage multiply the kW and MBH data from the table by the conversion factor in the following table DISTRIBUTI...

Page 13: ...6 45 45 6HK 0 1 6501006 40 49 3 53 8 50 60 6HK 1 2 6501306 52 62 5 68 5 70 70 6HK 1 2 6501506 60 70 9 77 7 80 80 6HK 1 2 6501806 72 84 1 92 4 90 100 6HK 1 2 6502006 80 92 5 101 7 100 110 36C 6HK 0 1...

Page 14: ...20 25 6HK 0 1 6500506 20 30 1 32 4 35 35 6HK 0 1 6500806 32 43 4 47 1 45 50 6HK 0 1 6501006 40 51 8 56 3 60 60 6HK 1 2 6501306 52 65 0 71 0 70 80 6HK 1 2 6501506 60 73 4 80 2 80 90 6HK 1 2 6501806 72...

Page 15: ...9 50 45 60 50 48C 6HK16501306 52 27 3 37 6 29 3 41 5 30 40 30 45 6HK16501506 60 30 2 43 3 32 5 47 9 35 45 35 50 6HK16501806 72 47 5 39 0 51 6 43 1 50 40 60 45 6HK16502006 80 51 8 43 3 56 4 47 9 50 45...

Page 16: ...6501025 23 1 28 3 30 9 30 35 6HK36501525 34 6 40 7 44 7 45 45 36B 6HK36501025 23 1 29 8 32 4 30 35 6HK36501525 34 6 42 2 46 2 45 50 6HK36501825 41 6 49 8 54 6 50 55 6HK46502025 46 2 54 8 60 1 55 70 36...

Page 17: ...l Code and local codes to determine correct wire sizing TABLE 11 Air Flow Data CFM 1 Models Blower Motor Speed External Static Pressure in wc 0 10 0 20 0 30 0 40 0 50 0 60 0 70 18B 5 HI 1132 1107 1074...

Page 18: ...ether to determine the total external system static pressure If a filter rack is installed on the return air end of the air handler or indoor coil sec tion make sure to measure the return air duct sta...

Page 19: ...nit Technical Guide Is the TXV bulb positioned correctly Is temperature bulb insulated Is equalizer line connected 3 MINIMUM HANDMADE TRAP PREMADE TRAPS SECONDARY PRIMARY WERE THE PRIMARY AND SECONDAR...

Page 20: ...AND NATIONAL CODES MUST BE FOLLOWED SEE INSTALLATION INSTRUCTIONS FOR PROPER LOW VOLTAGE FIELD WIRING CONNECTIONS LEGEND LS LIMIT SWITCH SEQ SEQUENCER HE HEATING ELEMENT FL FUSIBLE LINK H SEQUENCER H...

Page 21: ...N BLUE BLUE BLUE BLUE YELLOW YELLOW BLACK BLACK YELLOW YELLOW BLACK BLACK RED WHITE BLACK BLUE BLACK BLUE YELLOW BLACK YELLOW YELLOW BLUE BLACK BLUE BLACK YELLOW RLY 1 RLY 2 RLY 3 RLY 6 RLY 5 RLY 4 HE...

Page 22: ...6 22 Johnson Controls Unitary Products SECTION XVII TYPICAL THERMOSTAT CONNECTIONS FIGURE 23 Typical Thermostat Wiring Diagram ECM A0370 002 W2 X L X L X L X L FIELD INSTALLED JUMPER IF SINGLE STAGE T...

Page 23: ...dry bulb temperature Return air dry bulb temperature Temperature drop 1 2 3 4 5 Low Medium Low Medium Medium High High A B C D Outside air dry bulb temperature Return air wet bulb temperature Supply...

Page 24: ...oting and correcting any problems Operate the unit through cooling cycles from the thermostat noting and correcting any problems Operate the unit through mechanical heating cycles from the thermostat...

Reviews: