5169032-UIM-C-0416

Johnson Controls Unitary Products

17

TABLE 10: 

Electrical Data For Multi-source Power Supply: 208/230-3-60

Air Handlers 

Models

Heater

Models

1,2

Heater Amps 

@240V

Min. Circuit Ampacity

MOP

3

208V

230V

208V

230V

Circuit

Circuit

1st

3

2nd

1st

3

2nd

1st

3

2nd

1st

3

2nd

36B

6HK46502025

46.2

29.8

25.0

32.4

27.6

30

25

35

30

36C

6HK46502025

46.2

29.8

25.0

32.4

27.6

30

25

35

30

42C

6HK46502025

46.2

29.8

25.0

32.4

27.6

30

25

35

30

48C

6HK46502025

46.2

31.8

25.0

34.4

27.6

35

25

35

30

48D

6HK46502025

46.2

31.8

25.0

34.4

27.6

35

25

35

30

6HK46502525

57.7

38.0

31.3

41.3

34.6

40

35

45

35

60C

6HK46502025

46.2

31.8

25.0

34.4

27.6

35

25

35

30

60D

6HK46502025

46.2

31.8

25.0

34.4

27.6

35

25

35

30

6HK46502525

57.7

38.0

31.3

41.3

34.6

40

35

45

35

1.  (0,1) - 0 = no service disconnect OR 1 = with service disconnect.
2.  (1,2) - 1 = with service disconnect, no breaker jumper bar OR 2 = with service disconnect & breaker jumper bar. 
3.  MOP = Maximum Overcurrent Protection device; must be HACR type circuit breaker or time delay fuse. The 1st circuit includes blower motor amps. Refer to the 

 latest edition of the National Electric Code or in Canada the Canadian electrical Code and local codes to determine correct wire sizing.

TABLE 11: 

Air Flow Data (CFM)

1

Models

Blower 

Motor Speed

External Static Pressure (in. wc.)

0.10

0.20

0.30

0.40

0.50

0.60

0.70

18B

#5 HI

1132

1107

1074

1053

1023

990

955

#4 MED-HI

1025

994

971

943

912

878

803

#3 MED

821

798

764

727

657

599

536

#2 MED-LO

661

632

572

491

414

335

279

#1 LO

510

435

365

291

181

147

23

24B

#5 HI

1117

1078

1061

1034

1007

985

955

#4 MED-HI

1032

1001

975

946

928

898

872

#3 MED

838

799

768

742

698

634

582

#2 MED-LO

644

620

582

521

440

378

284

#1 LO

474

421

336

279

187

144

70

30B

#5 HI

1113

1083

1057

1034

1007

977

941

#4 MED-HI

1057

1021

1000

977

947

914

881

#3 MED

857

821

794

768

728

653

601

#2 MED-LO

675

641

607

533

460

408

345

#1 LO

489

457

386

324

261

209

158

36B

#5 HI

1323

1287

1264

1238

1210

1177

1149

#4 MED-HI

1255

1222

1193

1170

1140

1113

1081

#3 MED

1052

1025

992

967

927

857

811

#2 MED-LO

855

823

799

739

691

637

572

#1 LO

653

622

574

507

463

411

353

36C

#5 HI

1562

1531

1496

1453

1416

1381

1348

#4 MED-HI

1277

1240

1206

1165

1133

1083

1025

#3 MED

1078

1043

996

957

899

819

770

#2 MED-LO

881

836

810

749

658

578

537

#1 LO

707

677

595

524

451

405

346

42C

#5 HI

1594

1564

1530

1497

1459

1424

1382

#4 MED-HI

1442

1408

1374

1338

1298

1251

1199

#3 MED

1249

1215

1179

1135

1082

1016

956

#2 MED-LO

1048

1008

962

905

840

761

683

#1 LO

881

833

786

708

623

540

481

For notes, see Page 18.

Summary of Contents for AE SERIES

Page 1: ...nit may be used for upflow downflow horizontal right or horizontal left applications These units may be located in a closet utility room attic crawl space or basement These versatile models may be use...

Page 2: ...ons must be observed as applicable 12 These instructions cover minimum requirements and conform to existing national standards and safety codes In some instances these instructions exceed certain loca...

Page 3: ...ting any wiring duct work or piping FIGURE 2 Pressure Check A0271 001 DEPRESS SCHRADER CORE TO CHECK FOR PRESSURE ONE TIME NOTE Verify that the coil is under pressure when received FIGURE 3 Dimensions...

Page 4: ...allowing condensate to drain away from structure 5 When an indoor coil is installed in an attic or above a finished ceil ing an auxiliary drain pan should be provided under the air handler as is spec...

Page 5: ...short or where sound may be a problem acoustical duct liner should be used inside the duct Use flexible duct connectors to minimize the transmission of vibration noise into the conditioned space Insu...

Page 6: ...m be attached to the supply opening Refer to Figure 8 as a visual aid The use of this block off plate will enable better air circulation across the limit switches AIR FILTERS Return air filters are re...

Page 7: ...top of the pis ton distributor assembly Hand tighten and turn an additional 1 4 turn to seal Do not over tighten fittings 9 Replace black plastic cap on unused equalizer fitting connection port 10 Af...

Page 8: ...k position b If bulb installation is made on a vertical run ensure that the bulb is a minimum of 8 inches 20 3 cm away from elbow coming out of the coil Position the bulb with the tail of the bulb at...

Page 9: ...isolated by using appropriate hangers or strapping SECTION VII CONDENSATE DRAIN CONNECTIONS All drain lines should be trapped a minimum of three inches should be pitched away from unit drain pan and...

Page 10: ...uit should be terminated at the electrical control box To determine proper wire sizing refer to Tables 6 10 and the latest edition of the National Electric Code or in Canada the Canadian electrical Co...

Page 11: ...ppropriate speed tap according to Table 4 If electric heat requires speed tap 5 the highest speed tap available for cooling heat pump heating is tap 4 If a lower circulating speed is desired for fan o...

Page 12: ...Requirement For a power distribution voltage that is different than the provided nominal voltage multiply the kW and MBH data from the table by the conversion factor in the following table DISTRIBUTI...

Page 13: ...6 45 45 6HK 0 1 6501006 40 49 3 53 8 50 60 6HK 1 2 6501306 52 62 5 68 5 70 70 6HK 1 2 6501506 60 70 9 77 7 80 80 6HK 1 2 6501806 72 84 1 92 4 90 100 6HK 1 2 6502006 80 92 5 101 7 100 110 36C 6HK 0 1...

Page 14: ...20 25 6HK 0 1 6500506 20 30 1 32 4 35 35 6HK 0 1 6500806 32 43 4 47 1 45 50 6HK 0 1 6501006 40 51 8 56 3 60 60 6HK 1 2 6501306 52 65 0 71 0 70 80 6HK 1 2 6501506 60 73 4 80 2 80 90 6HK 1 2 6501806 72...

Page 15: ...9 50 45 60 50 48C 6HK16501306 52 27 3 37 6 29 3 41 5 30 40 30 45 6HK16501506 60 30 2 43 3 32 5 47 9 35 45 35 50 6HK16501806 72 47 5 39 0 51 6 43 1 50 40 60 45 6HK16502006 80 51 8 43 3 56 4 47 9 50 45...

Page 16: ...6501025 23 1 28 3 30 9 30 35 6HK36501525 34 6 40 7 44 7 45 45 36B 6HK36501025 23 1 29 8 32 4 30 35 6HK36501525 34 6 42 2 46 2 45 50 6HK36501825 41 6 49 8 54 6 50 55 6HK46502025 46 2 54 8 60 1 55 70 36...

Page 17: ...l Code and local codes to determine correct wire sizing TABLE 11 Air Flow Data CFM 1 Models Blower Motor Speed External Static Pressure in wc 0 10 0 20 0 30 0 40 0 50 0 60 0 70 18B 5 HI 1132 1107 1074...

Page 18: ...ether to determine the total external system static pressure If a filter rack is installed on the return air end of the air handler or indoor coil sec tion make sure to measure the return air duct sta...

Page 19: ...nit Technical Guide Is the TXV bulb positioned correctly Is temperature bulb insulated Is equalizer line connected 3 MINIMUM HANDMADE TRAP PREMADE TRAPS SECONDARY PRIMARY WERE THE PRIMARY AND SECONDAR...

Page 20: ...AND NATIONAL CODES MUST BE FOLLOWED SEE INSTALLATION INSTRUCTIONS FOR PROPER LOW VOLTAGE FIELD WIRING CONNECTIONS LEGEND LS LIMIT SWITCH SEQ SEQUENCER HE HEATING ELEMENT FL FUSIBLE LINK H SEQUENCER H...

Page 21: ...N BLUE BLUE BLUE BLUE YELLOW YELLOW BLACK BLACK YELLOW YELLOW BLACK BLACK RED WHITE BLACK BLUE BLACK BLUE YELLOW BLACK YELLOW YELLOW BLUE BLACK BLUE BLACK YELLOW RLY 1 RLY 2 RLY 3 RLY 6 RLY 5 RLY 4 HE...

Page 22: ...6 22 Johnson Controls Unitary Products SECTION XVII TYPICAL THERMOSTAT CONNECTIONS FIGURE 23 Typical Thermostat Wiring Diagram ECM A0370 002 W2 X L X L X L X L FIELD INSTALLED JUMPER IF SINGLE STAGE T...

Page 23: ...dry bulb temperature Return air dry bulb temperature Temperature drop 1 2 3 4 5 Low Medium Low Medium Medium High High A B C D Outside air dry bulb temperature Return air wet bulb temperature Supply...

Page 24: ...oting and correcting any problems Operate the unit through cooling cycles from the thermostat noting and correcting any problems Operate the unit through mechanical heating cycles from the thermostat...

Reviews: