background image

835964-UIM-A-0112

6

Johnson Controls Unitary Products

SECTION VII: SYSTEM CHARGE

The factory charge in the outdoor unit includes enough charge for the
unit, a 15 ft. (4.6 m) line set, and the smallest indoor coil match-up.
Some indoor coil matches may require additional charge. See tabular
data sheet provided in unit literature packet for charge requirements.

The “TOTAL SYSTEM CHARGE” must be permanently stamped on the
unit data plate.

Total system charge is determined as follows:

1.

Determine outdoor unit charge from tabular data sheet.

2.

Determine indoor coil adjustment from tabular data sheet.

3.

Calculate the line charge using the tabular data sheet if line length
is greater than 15 feet (4.6 m).

4.

Total system charge = item 1 + item 2 + item 3.

5.

Permanently stamp the unit data plate with the total amount of
refrigerant in the system.

Use the following charging method whenever additional refrigerant is
required for the system charge.

If a calibrated charging cylinder or accurate weighing device is avail-
able, add refrigerant accordingly. Otherwise, model-specific charging
charts are provided on the access panel of the unit.

SUPERHEAT CHARGING METHOD - 

PISTON INDOOR

1.

Set the system running in cooling mode by setting the thermostat
at least 6°F below the room temperature and operate system for at
least 10 – 15 minutes.

2.

Refer to the technical guide for the recommended airflow and ver-
ify indoor airflow (it should be about 400 SCFM per ton).

3.

Measure and record the outdoor ambient (DB) temperature and
the suction pressure at the suction service valve.

4.

Using the charging chart located on the unit, find the intersection
of the outdoor ambient dry bulb and the suction pressure obtained
in step 3. This is the recommended suction tube temperature at
the service valve.

5.

Measure and record the suction tube temperature at the service
valve and compare to the recommended temperature obtained in
step 4.

6.

Add charge if the measured suction temperature in step 5 is above
the recommended value. Remove / recover refrigerant if the mea-
sured suction temperature is below the recommended value.

SUBCOOLING CHARGING METHOD - TXV INDOOR

For cooling operation, unless otherwise specified, the default subcool-
ing is 10°F.

1.

Set the system running in cooling mode by setting the thermostat
at least 6°F below the room temperature and operate system for at
least 10 – 15 minutes.

2.

Refer to the technical guide for the recommended indoor airflow
and verify it is correct (it should be about 400 SCFM per ton).

3.

Measure and record the indoor wet bulb (WB) and the outdoor
ambient dry bulb (DB) temperature.

4.

Using the charging chart located on the unit, find the intersection
of the indoor wet bulb and the outdoor dry bulb. This is the recom-
mended liquid pressure (and subcooling value).

5.

Measure and record the pressure at the liquid valve pressure port
and compare to the value obtained in step 4.

6.

Add charge if the measured liquid pressure is lower than the rec-
ommended value. Remove / recover charge if the measured liquid
pressure is above the recommended value.

Condenser subcooling is obtained by calculating the difference of the
saturated refrigerant temperature of the pressure measured at the liquid
base valve and the liquid tube temperature as measured at the liquid
base valve.

Subcooling Temp. (TC) = Saturated Temp. (TS) – Liquid Temp. (T).

Do not leave the system open to the atmosphere.

DO NOT attempt to pump “Total System Charge” into outdoor unit
for maintenance, service, etc. This may cause damage to the com-
pressor and/or other components. the outdoor unit only has enough
volume for the factory charge, not the “Total System Charge”.

Refrigerant charging should only be carried out by a qualified air
conditioning contractor.

Compressor damage will occur if system is improperly charged. On
new system installations, charge system per tabular data sheet for
the matched coil and follow guidelines in this instruction.

Example: The suction tube temperature listed on the table at the 
intersection of the outdoor DB and the suction pressure is 63°F. 
Temperature of the suction tube at the service valve is 68°F. It would 
be necessary to add refrigerant to drop the suction tube temperature 
to 63°F.

Example: The liquid pressure listed at the intersection of the indoor 
WB and the outdoor DB 320 psig. Pressure at the liquid valve is 305 
psig. It would be necessary to add refrigerant to increase the liquid 
pressure to 320 psig.

IT IS UNLAWFUL TO KNOWINGLY VENT, RELEASE OR DIS-
CHARGE REFRIGERANT INTO THE OPEN AIR DURING
REPAIR, SERVICE, MAINTENANCE OR THE FINAL DISPOSAL
OF THIS UNIT.

Summary of Contents for 13 Seer-GCGD

Page 1: ...hazardous situation which if not avoided will result in death or serious injury WARNING indicates a potentially hazardous situation which if not avoided could result in death or serious injury CAUTIO...

Page 2: ...410A coil con densing unit combination with the appropriate metering device 2 Change out of the line set when replacing an R 22 unit with an R410 A unit is highly recommended to reduce cross contamina...

Page 3: ...o avoid sharp bends which may cause a restriction 2 The lines should be installed so that they will not obstruct service access to the coil air handling system or filter 3 Care must also be taken to i...

Page 4: ...ER TIGHTEN between 40 and 60 inch lbs maximum 10 Evacuate the vapor line evaporator and liquid line to 500 microns or less 11 Replace cap on service ports Do not remove the flare caps from the service...

Page 5: ...r fitting and an additional 1 3 turn to seal 7 Install the TXV bulb to the vapor line near the equalizer line using the bulb clamp s furnished with the TXV assembly Ensure the bulb is making maximum c...

Page 6: ...e default subcool ing is 10 F 1 Set the system running in cooling mode by setting the thermostat at least 6 F below the room temperature and operate system for at least 10 15 minutes 2 Refer to the te...

Page 7: ...ly connections TABLE 2 R 410A Saturation Properties TEMP F PRESSURE PSIG TEMP F PRESSURE PSIG TEMP F PRESSURE PSIG TEMP F PRESSURE PSIG TEMP F PRESSURE PSIG 45 130 60 170 75 217 90 274 105 341 46 132...

Page 8: ...unit and thermostat To eliminate erratic operation seal the hole in the wall at the ther mostat with permagum or equivalent to prevent air drafts affecting the operation of in the thermostat NOTICE FI...

Page 9: ...electric heat on thermostat is not necessary MA SHP AHP ID MODELS Other Part Numbers SAP Legacy 265902 031 09167 2 Part Numbers SAP Legacy 159480 031 09156 1 COM 24 Volt Common R 24 Volt Hot W2 Secon...

Page 10: ...Y1 Single Stage Compressor Y Y2 Second or Full Stage Compressor W1 First Stage Heat Y Full Stage Compressor G Fan BP11C50124 BN11C01124 DP11C40124 DN11C00124 THERMOSTAT RH 24 Volt Hot Heat XFMR RC 24...

Page 11: ...ll Stage Heat Clipping Jumper W914 for electric heat on thermostat is not necessary 24VAC Humidifier Optional C 24 Volt Common Y Compressor SINGLE STAGE AIR CONDITIONER Y Compressor Contactor SINGLE S...

Page 12: ...rmostat is not necessary C 24 Volt Common Y Full Stage Compressor G Fan BN11C00124 THERMOSTAT RH 24 Volt Hot Heat XFMR RC 24 Volt Hot Cool XFMR W Full Stage Heat Thermostat Installer Setup 1 System Ty...

Page 13: ...ration and maintenance of all other system components MAINTENANCE 1 Dirt should not be allowed to accumulate on the outdoor coils or other parts in the air circuit Clean as often as necessary to keep...

Page 14: ...835964 UIM A 0112 14 Johnson Controls Unitary Products SECTION X WIRING DIAGRAM FIGURE 14 Wiring Diagram Single Phase 167242...

Page 15: ...835964 UIM A 0112 Johnson Controls Unitary Products 15 FIGURE 15 Wiring Diagram Three Phase 412217...

Page 16: ...ge without notice Published in U S A 835964 UIM A 0112 Copyright 2012 by Johnson Controls Inc All rights reserved Supersedes 414172 UIM D 1211 Johnson Controls Unitary Products 5005 York Drive Norman...

Reviews: