835964-UIM-A-0112

Johnson Controls Unitary Products

9

For additional connection diagrams for all UPG equipment refer to “Low Voltage System Wiring” document available online at www.upgnet.com in the
Product Catalog Section.

 FIGURE 10:  

Thermostat Chart - Single Stage AC with PSC Air Handler

AC 1A

Single Stage Air Conditioner

– PSC Air Handler

C

24 – Volt Common

Y

Compressor

SINGLE STAGE

AIR CONDITIONER

SINGLE STAGE

AIR CONDITIONER

HM1

Humidistat

Y

Full Stage Compressor

G

Fan

*PP11C70224

THERMOSTAT

RH

24 – Volt Hot

(Heat XFMR)

RC

24 – Volt Hot
(Cool XFMR)

W

Full Stage Heat

Clipping Jumper W914 for

electric heat on thermostat

is not necessary

MA

SHP

AHP

ID MODELS

Other Part Numbers:

SAP   =    Legacy

265902  =  031-09167

2

Part Numbers:

SAP   =    Legacy

159480  =  031-09156

1

COM

24 – Volt Common

R

24 – Volt Hot

W2

Second Stage Heat

O

Reversing Valve

Energized in Cool

X/L

Malfunction Light

HUM

Humidity Switch

Open on Humidity Rise

PSC

AIR HANDLER CONTROL

G

Fan

PSC

AIR HANDLER

1

EAC(24 VAC out)

Electronic Air Cleaner

HUM OUT

(24 VAC out)

Humidifier

Y1

Single Stage Compressor

Y/Y2

Second or Full 

Stage Compressor

W1

First Stage Heat

24VAC Humidifier

(Optional)

24VAC

Electronic Air Cleaner

(Optional)

Y

Compressor Contactor

SINGLE STAGE

AIR

CONDITIONER

SINGLE STAGE

AIR CONDITIONER

Move HUM STAT

jumper to “YES”

if humidistat is to be used. 

Refer to AH documentation

for W1 and W2 electric

heat staging options. 

Summary of Contents for 13 Seer-GCGD

Page 1: ...hazardous situation which if not avoided will result in death or serious injury WARNING indicates a potentially hazardous situation which if not avoided could result in death or serious injury CAUTIO...

Page 2: ...410A coil con densing unit combination with the appropriate metering device 2 Change out of the line set when replacing an R 22 unit with an R410 A unit is highly recommended to reduce cross contamina...

Page 3: ...o avoid sharp bends which may cause a restriction 2 The lines should be installed so that they will not obstruct service access to the coil air handling system or filter 3 Care must also be taken to i...

Page 4: ...ER TIGHTEN between 40 and 60 inch lbs maximum 10 Evacuate the vapor line evaporator and liquid line to 500 microns or less 11 Replace cap on service ports Do not remove the flare caps from the service...

Page 5: ...r fitting and an additional 1 3 turn to seal 7 Install the TXV bulb to the vapor line near the equalizer line using the bulb clamp s furnished with the TXV assembly Ensure the bulb is making maximum c...

Page 6: ...e default subcool ing is 10 F 1 Set the system running in cooling mode by setting the thermostat at least 6 F below the room temperature and operate system for at least 10 15 minutes 2 Refer to the te...

Page 7: ...ly connections TABLE 2 R 410A Saturation Properties TEMP F PRESSURE PSIG TEMP F PRESSURE PSIG TEMP F PRESSURE PSIG TEMP F PRESSURE PSIG TEMP F PRESSURE PSIG 45 130 60 170 75 217 90 274 105 341 46 132...

Page 8: ...unit and thermostat To eliminate erratic operation seal the hole in the wall at the ther mostat with permagum or equivalent to prevent air drafts affecting the operation of in the thermostat NOTICE FI...

Page 9: ...electric heat on thermostat is not necessary MA SHP AHP ID MODELS Other Part Numbers SAP Legacy 265902 031 09167 2 Part Numbers SAP Legacy 159480 031 09156 1 COM 24 Volt Common R 24 Volt Hot W2 Secon...

Page 10: ...Y1 Single Stage Compressor Y Y2 Second or Full Stage Compressor W1 First Stage Heat Y Full Stage Compressor G Fan BP11C50124 BN11C01124 DP11C40124 DN11C00124 THERMOSTAT RH 24 Volt Hot Heat XFMR RC 24...

Page 11: ...ll Stage Heat Clipping Jumper W914 for electric heat on thermostat is not necessary 24VAC Humidifier Optional C 24 Volt Common Y Compressor SINGLE STAGE AIR CONDITIONER Y Compressor Contactor SINGLE S...

Page 12: ...rmostat is not necessary C 24 Volt Common Y Full Stage Compressor G Fan BN11C00124 THERMOSTAT RH 24 Volt Hot Heat XFMR RC 24 Volt Hot Cool XFMR W Full Stage Heat Thermostat Installer Setup 1 System Ty...

Page 13: ...ration and maintenance of all other system components MAINTENANCE 1 Dirt should not be allowed to accumulate on the outdoor coils or other parts in the air circuit Clean as often as necessary to keep...

Page 14: ...835964 UIM A 0112 14 Johnson Controls Unitary Products SECTION X WIRING DIAGRAM FIGURE 14 Wiring Diagram Single Phase 167242...

Page 15: ...835964 UIM A 0112 Johnson Controls Unitary Products 15 FIGURE 15 Wiring Diagram Three Phase 412217...

Page 16: ...ge without notice Published in U S A 835964 UIM A 0112 Copyright 2012 by Johnson Controls Inc All rights reserved Supersedes 414172 UIM D 1211 Johnson Controls Unitary Products 5005 York Drive Norman...

Reviews: