background image

835964-UIM-A-0112

Johnson Controls Unitary Products

3

GROUND INSTALLATION

The unit should be installed on a solid base that is 2” (5.1 cm) above
grade and will not shift or settle, causing strain on the refrigerant lines
and possible leaks. Maintain the clearances shown in Figure 1 and
install the unit in a level position. The base pad should not come in con-
tact with the foundation or side of the structure because sound may be
transmitted to the residence.

The length of the refrigerant tubing between the outdoor unit and indoor
coil should be as short as possible to avoid capacity and efficiency
losses. Excessive spacing of the outdoor unit from the home can result
in the refrigerant lines being restricted by trampling or being punctured
by lawn mowers. Locate the outdoor unit away from bedroom windows
or other rooms where sound might be objectionable.

Adverse effects of snow or sleet accumulating on the outdoor coil can
be eliminated by placing the outdoor unit where the prevailing wind
does not blow across the unit. Trees, shrubs, corners of buildings, and
fences standing off from the coil can reduce capacity loss due to wind
chill effect.

Provide ample clearance from shrubs to allow adequate air to pass
across the outdoor coil without leaves or branches being pulled into the
coil.

ROOF INSTALLATION

When installing units on a roof, the structure must be capable of sup-
porting the total weight of the unit, including a pad, lintels, rails, etc.,
which should be used to minimize the transmission of sound or vibra-
tion into the conditioned space.

LIQUID LINE FILTER-DRIER

The air conditioning unit’s filter/dryer is located on the liquid line.

PIPING CONNECTIONS

The outdoor condensing unit must be connected to the indoor evapora-
tor coil using field supplied refrigerant grade (ACR) copper tubing that is
internally clean and dry. Units should be installed only with the tubing
sizes for approved system combinations as specified in tabular data
sheet. The charge given is applicable for total tubing lengths up to 15
feet (4.6 m). See Application Data Part Number 247077 for installing
tubing of longer lengths and elevation differences.

PRECAUTIONS DURING LINE INSTALLATION

1.

Install the lines with as few bends as possible. Care must be taken
not to damage the couplings or kink the tubing. Use clean hard
drawn copper tubing where no appreciable amount of bending
around obstruction is necessary. If soft copper must be used, care
must be taken to avoid sharp bends which may cause a restriction.

2.

The lines should be installed so that they will not obstruct service
access to the coil, air handling system, or filter.

3.

Care must also be taken to isolate the refrigerant lines to minimize
noise transmission from the equipment to the structure.

4.

The vapor line must be insulated with a minimum of 1/2" foam rub-
ber insulation (Armaflex or equivalent). Liquid lines that will be
exposed to direct sunlight, high temperatures, or excessive humid-
ity must also be insulated.

5.

Tape and suspend the refrigerant lines as shown. DO NOT allow
tube metal-to-metal contact. See Figure 2.

6.

Use PVC piping as a conduit for all underground installations as
shown in Figure 3. Buried lines should be kept as short as possible
to minimize the build up of liquid refrigerant in the vapor line during
long periods of shutdown.

7.

Pack fiberglass insulation and a sealing material such as perma-
gum around refrigerant lines where they penetrate a wall to reduce
vibration and to retain some flexibility.

8.

For systems with total line length exceeding 70 feet (21.3 m), see
APPLICATION DATA and worksheet  "General Piping Recommen-
dations and Refrigerant Line Length" for vapor and liquid line siz-
ing, calibration of liquid line pressure loss or gain, determination of
vapor line velocity, elevation limitations, orifice connections, sys-
tem charging, traps, etc.

Replacements for the liquid line drier must be exactly the same as
marked on the original factory drier. See Source1 for O.E.M.
replacement driers.

Failure to do so or using a substitute drier or a granular type may
result in damage to the equipment.

Filter-Drier

Source 1 Part No.

Apply with Models

S1-02922195000

All

Using a larger than specified line size could result in oil return prob-
lems. Using too small a line will result in loss of capacity and other
problems caused by insufficient refrigerant flow. Slope horizontal
vapor lines at least 1" (2.5 cm) every 20 feet (6.1 m) toward the out-
door unit to facilitate proper oil return.

NOTICE

NOTICE

This system uses R-410A refrigerant which operates at higher pres-
sures than R-22. No other refrigerant may be used in this system.
Gauge sets, hoses, refrigerant containers, and recovery system
must be designed to handle R-410A. If you are unsure, consult the
equipment manufacturer.

Never install a suction-line filter drier in the liquid line of an R-410A
system. Failure to follow this warning can cause a fire, injury or
death.

 FIGURE 2:  

Installation of Vapor Line

 FIGURE 3:  

Underground Installation

Liquid
Line

Incorrect

Correct

Tape

Sheet Metal Hanger

TO INDOOR COIL

Liquid Line

PVC
Conduit

Insulated
Vapor Line

TO OUTDOOR UNIT

Cap

Summary of Contents for 13 Seer-GCGD

Page 1: ...hazardous situation which if not avoided will result in death or serious injury WARNING indicates a potentially hazardous situation which if not avoided could result in death or serious injury CAUTIO...

Page 2: ...410A coil con densing unit combination with the appropriate metering device 2 Change out of the line set when replacing an R 22 unit with an R410 A unit is highly recommended to reduce cross contamina...

Page 3: ...o avoid sharp bends which may cause a restriction 2 The lines should be installed so that they will not obstruct service access to the coil air handling system or filter 3 Care must also be taken to i...

Page 4: ...ER TIGHTEN between 40 and 60 inch lbs maximum 10 Evacuate the vapor line evaporator and liquid line to 500 microns or less 11 Replace cap on service ports Do not remove the flare caps from the service...

Page 5: ...r fitting and an additional 1 3 turn to seal 7 Install the TXV bulb to the vapor line near the equalizer line using the bulb clamp s furnished with the TXV assembly Ensure the bulb is making maximum c...

Page 6: ...e default subcool ing is 10 F 1 Set the system running in cooling mode by setting the thermostat at least 6 F below the room temperature and operate system for at least 10 15 minutes 2 Refer to the te...

Page 7: ...ly connections TABLE 2 R 410A Saturation Properties TEMP F PRESSURE PSIG TEMP F PRESSURE PSIG TEMP F PRESSURE PSIG TEMP F PRESSURE PSIG TEMP F PRESSURE PSIG 45 130 60 170 75 217 90 274 105 341 46 132...

Page 8: ...unit and thermostat To eliminate erratic operation seal the hole in the wall at the ther mostat with permagum or equivalent to prevent air drafts affecting the operation of in the thermostat NOTICE FI...

Page 9: ...electric heat on thermostat is not necessary MA SHP AHP ID MODELS Other Part Numbers SAP Legacy 265902 031 09167 2 Part Numbers SAP Legacy 159480 031 09156 1 COM 24 Volt Common R 24 Volt Hot W2 Secon...

Page 10: ...Y1 Single Stage Compressor Y Y2 Second or Full Stage Compressor W1 First Stage Heat Y Full Stage Compressor G Fan BP11C50124 BN11C01124 DP11C40124 DN11C00124 THERMOSTAT RH 24 Volt Hot Heat XFMR RC 24...

Page 11: ...ll Stage Heat Clipping Jumper W914 for electric heat on thermostat is not necessary 24VAC Humidifier Optional C 24 Volt Common Y Compressor SINGLE STAGE AIR CONDITIONER Y Compressor Contactor SINGLE S...

Page 12: ...rmostat is not necessary C 24 Volt Common Y Full Stage Compressor G Fan BN11C00124 THERMOSTAT RH 24 Volt Hot Heat XFMR RC 24 Volt Hot Cool XFMR W Full Stage Heat Thermostat Installer Setup 1 System Ty...

Page 13: ...ration and maintenance of all other system components MAINTENANCE 1 Dirt should not be allowed to accumulate on the outdoor coils or other parts in the air circuit Clean as often as necessary to keep...

Page 14: ...835964 UIM A 0112 14 Johnson Controls Unitary Products SECTION X WIRING DIAGRAM FIGURE 14 Wiring Diagram Single Phase 167242...

Page 15: ...835964 UIM A 0112 Johnson Controls Unitary Products 15 FIGURE 15 Wiring Diagram Three Phase 412217...

Page 16: ...ge without notice Published in U S A 835964 UIM A 0112 Copyright 2012 by Johnson Controls Inc All rights reserved Supersedes 414172 UIM D 1211 Johnson Controls Unitary Products 5005 York Drive Norman...

Reviews: