53
Maintenance
Normal Maintenance
Filters
Inspect once a month. Replace disposable or clean permanent
type as necessary. DO NOT replace permanent type with
disposable. The dimensional size of the replacement filter must
be the same as the replaced filter.
Motors
Outdoor fan motors are permanently lubricated and require no
maintenance.
Indoor Blower Motor and Drive - The indoor blower motor
features ball bearings that do not require periodic lubrication.
On an annual basis, check the motor for accumulations of dust,
etc. that may block the cooling slots in the motor shell. Check
for loose, damaged or misaligned drive components. Check
that all mounting bolts are tight. Replace defective parts as
required.
Outdoor Coil
Dirt should not be allowed to accumulate on the outdoor coil
surface or other parts in the air circuit. Cleaning should be as
often as necessary to keep coil clean. Use a brush, vacuum
cleaner attachment, or other suitable means. If water is used to
clean coil, be sure electric power to the unit is shut off prior to
cleaning.
NOTE:
Exercise care when cleaning the coil so that the coil fins
are not damaged.
Table 21: Cable for FC Buses and SA Buses in Order of Preference
Bus and Cable Type
Non-Plenum Applications
Plenum Applications
Part Number
O.D.
Part Number
O.D.
FC Bus:
22 AWG Stranded, 3-Wire Twisted Shielded Cable
1
1. We strongly recommend 3-wire (for FC bus) and 4-wire, 2 twisted-pair (for SA bus), 22 AWG stranded, shielded cable. A 22 gauge cable
offers the best performance for various baud rates, cable distances, and number of trunk devices primarily due to lower conductor-to-
conductor capacitance. Shielded cable offers better overall electrical noise immunity than non-shielded cable. Observe the shield
grounding requirements.
Anixter:
CBL-22/3-FC-PVC
Belden®: B5501FE
0.138 in.
Anixter: CBL-22/3-FC-PLN
Belden: B6501FE
0.140 in.
SA Bus (Terminal Block):
22 AWG Stranded, 4-Wire, 2 Twisted-
Pair Shielded Cable
Anixter:
CBL-22/2P-SA-PVC
Belden: B5541FE
0.209 in.
Anixter: CBL-22/2P-SA-PLN
Belden: B6541FE
0.206 in.
SA Bus (Modular Jack):
26 AWG Solid 6-Wire, 3 Twisted-Pair Cable
2
2. We recommend 26 AWG solid, 6-wire (3 twisted pairs) cable as the best fit for fabricating modular cables with the modular jack housing
assembly. Be sure the cable you use fits the modular jack housing. The preassembled cables that are available from Anixter (Part No.
CBL-NETWORKxxx) use 24 gauge wire.
—
—
Anixter preassembled: CBL-
NETWORK25 CBL-
NETWORK50 CBL-
NETWORK75 CBL-
NETWORK100
0.15 in.
FC Bus:
22 AWG Stranded, 3-Wire Twisted Non-Shielded Cable
Belden: B5501UE
0.135 in.
Belden: B6501UE
0.131 in.
SA Bus (Terminal Block):
22 AWG Stranded, 4-Wire, 2 Twisted-
Pair Non-Shielded Cable
Belden: B5541UE
0.206 in.
Belden: B6541UE
0.199 in.
Prior to any of the following maintenance procedures,
shut off all electric power to the unit to prevent personal
injury.
Perform all maintenance operations on the blower motor
with electric power disconnected from the unit.