5188238-YIM-D-0518
26
Johnson Controls Ducted Systems
XN036-060 - With Powered Convenience Outlet (Direct Drive)
Size
(Tons)
Volt
Compressors
(each)
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Conv
Outlet
Electric Heat Option
MCA
1
(Amps)
Max
Fuse
2
/
Breaker
3
Size
(Amps)
RLA LRA MCC
FLA
FLA
FLA
Model
kW
Stages
Amps
036
(3.0)
208-1-60 16.7
109
26
1.3
6
10
NONE
-
-
-
38.2
50
E05
4
1
19.2
62.2
70
E07
5.6
1
26.9
71.8
80
E10
8
1
38.5
86.3
90
E15
11.9
2
57.2
109.7
110
E20
15.9
2
76.4
133.7
150
230-1-60 16.7
109
26
1.3
6
10
NONE
-
-
-
38.2
50
E05
5.3
1
22.1
65.8
70
E07
7.5
1
31.2
77.2
80
E10
10.6
1
44.2
93.4
100
E15
15.9
2
66.2
121
125
E20
21.2
2
88.3
148.6
150
208-3-60 11.2
88
17.5
1.3
6
10
NONE
-
-
-
31.3
40
E05
4
1
11.1
45.2
50
E07
5.6
1
15.5
50.7
60
E10
8
1
22.2
59.1
60
E15
11.9
2
33
72.6
80
E20
15.9
2
44.1
86.5
90
230-3-60 11.2
88
17.5
1.3
6
10
NONE
-
-
-
31.3
40
E05
5.3
1
12.7
47.2
50
E07
7.5
1
18
53.9
60
E10
10.6
1
25.5
63.2
70
E15
15.9
2
38.2
79.1
80
E20
21.2
2
51
95
100
048
(4.0)
208-1-60 19.6
130
30.5
2.8
7.6
10
NONE
-
-
-
44.9
60
E05
4
1
19.2
68.9
80
E07
5.6
1
26.9
78.6
90
E10
8
1
38.5
93
100
E15
11.9
2
57.2
116.4
125
E20
15.9
2
76.4
140.5
150
230-1-60 19.6
130
30.5
2.8
7.6
10
NONE
-
-
-
44.9
60
E05
5.3
1
22.1
72.5
80
E07
7.5
1
31.2
84
90
E10
10.6
1
44.2
100.1
110
E15
15.9
2
66.2
127.7
150
E20
21.2
2
88.3
155.3
175
208-3-60 13.7 83.1
21.4
2.8
7.6
10
NONE
-
-
-
37.5
50
E05
4
1
11.1
51.4
60
E07
5.6
1
15.5
57
60
E10
8
1
22.2
65.3
70
E15
11.9
2
33
78.8
80
E20
15.9
2
44.1
92.7
100
230-3-60 13.7 83.1
21.4
2.8
7.6
10
NONE
-
-
-
37.5
50
E05
5.3
1
12.7
53.5
60
E07
7.5
1
18
60.1
70
E10
10.6
1
25.5
69.4
70
E15
15.9
2
38.2
85.3
90
E20
21.2
2
51
101.3
110