5188238-YIM-D-0518
Johnson Controls Ducted Systems
21
060
(5.0)
208-1-60 27.1 152.9 42.3
2.8
7.6
0
NONE
-
-
-
44.3
60
E05
4
1
19.2
68.3
90
E07
5.6
1
26.9
77.9
90
E10
8
1
38.5
92.4
100
E15
11.9
2
57.2
115.8
125
E20
15.9
2
76.4
139.8
150
E30
22.2
2
106.7
177.7
200
230-1-60 27.1 152.9 42.3
2.8
7.6
0
NONE
-
-
-
44.3
60
E05
5.3
1
22.1
71.9
90
E07
7.5
1
31.2
83.3
100
E10
10.6
1
44.2
99.5
110
E15
15.9
2
66.2
127.1
150
E20
21.2
2
88.3
154.7
175
E30
29.6
2
123.3
198.4
200
208-3-60 16.5
110
25.8
2.8
7.6
0
NONE
-
-
-
31
40
E05
4
1
11.1
44.9
50
E07
5.6
1
15.5
50.5
60
E10
8
1
22.2
58.8
60
E15
11.9
2
33
72.3
80
E20
15.9
2
44.1
86.2
90
E30
22.2
2
61.6
108.1
110
230-3-60 16.5
110
25.8
2.8
7.6
0
NONE
-
-
-
31
40
E05
5.3
1
12.7
47
60
E07
7.5
1
18
53.6
60
E10
10.6
1
25.5
62.9
70
E15
15.9
2
38.2
78.8
80
E20
21.2
2
51
94.8
100
E30
29.6
2
71.2
120
125
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
XN036-060 - Without Powered Convenience Outlet (Direct Drive) (Continued)
Size
(Tons)
Volt
Compressors
(each)
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Conv
Outlet
Electric Heat Option
MCA
1
(Amps)
Max
Fuse
2
/
Breaker
3
Size
(Amps)
RLA LRA MCC
FLA
FLA
FLA
Model
kW
Stages
Amps