5188238-YIM-D-0518
Johnson Controls Ducted Systems
17
060
(5.0)
208-1-60 27.1 152.9 42.3
2.8
4.3
0
NONE
-
-
-
41
50
E05
4
1
19.2
65
80
E07
5.6
1
26.9
74.6
90
E10
8
1
38.5
89.1
100
E15
11.9
2
57.2
112.5
125
E20
15.9
2
76.4
136.5
150
E30
22.2
2
106.7
174.4
175
230-1-60 27.1 152.9 42.3
2.8
4.3
0
NONE
-
-
-
41
50
E05
5.3
1
22.1
68.6
90
E07
7.5
1
31.2
80
90
E10
10.6
1
44.2
96.2
110
E15
15.9
2
66.2
123.8
125
E20
21.2
2
88.3
151.4
175
E30
29.6
2
123.3
195.1
200
208-3-60 16.5
110
25.8
2.8
4.3
0
NONE
-
-
-
27.7
35
E05
4
1
11.1
41.6
50
E07
5.6
1
15.5
47.2
50
E10
8
1
22.2
55.5
60
E15
11.9
2
33
69
70
E20
15.9
2
44.1
82.9
90
E30
22.2
2
61.6
104.8
110
230-3-60 16.5
110
25.8
2.8
4.3
0
NONE
-
-
-
27.7
35
E05
5.3
1
12.7
43.7
50
E07
7.5
1
18
50.3
60
E10
10.6
1
25.5
59.6
60
E15
15.9
2
38.2
75.5
80
E20
21.2
2
51
91.5
100
E30
29.6
2
71.2
116.7
125
460-3-60 7.2
52
11.3
2.8
2.1
0
NONE
-
-
-
12.5
15
E07
6.8
1
8.2
22.7
25
E10
10.1
1
12.1
27.7
30
E15
13.6
2
16.4
32.9
35
E20
19.5
2
23.5
41.8
45
E30
28.8
2
34.6
55.8
60
575-3-60 5.5
38.9
8.6
2.8
1.9
0
NONE
-
-
-
9.9
15
E10
10.6
1
10.2
22.6
25
E15
15.9
2
15.3
29
30
E20
21.2
2
20.4
35.4
40
E30
30.4
2
29.3
46.5
50
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
XN036-060 - Without Powered Convenience Outlet (Belt Drive) (Continued)
Size
(Tons)
Volt
Compressors
(each)
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Conv
Outlet
Electric Heat Option
MCA
1
(Amps)
Max
Fuse
2
/
Breaker
3
Size
(Amps)
RLA LRA MCC
FLA
FLA
FLA
Model
kW
Stages
Amps