5188238-YIM-D-0518
Johnson Controls Ducted Systems
23
060
(5.0)
208-1-60 27.1 152.9 42.3
2.8
4.3
10
NONE
-
-
-
51
70
E05
4
1
19.2
75
90
E07
5.6
1
26.9
84.6
100
E10
8
1
38.5
99.1
110
E15
11.9
2
57.2
122.5
125
E20
15.9
2
76.4
146.5
150
E30
22.2
2
106.7
184.4
200
230-1-60 27.1 152.9 42.3
2.8
4.3
10
NONE
-
-
-
51
70
E05
5.3
1
22.1
78.6
100
E07
7.5
1
31.2
90
100
E10
10.6
1
44.2
106.2
110
E15
15.9
2
66.2
133.8
150
E20
21.2
2
88.3
161.4
175
E30
29.6
2
123.3
205.1
225
208-3-60 16.5
110
25.8
2.8
4.3
10
NONE
-
-
-
37.7
50
E05
4
1
11.1
51.6
60
E07
5.6
1
15.5
57.2
60
E10
8
1
22.2
65.5
70
E15
11.9
2
33
79
80
E20
15.9
2
44.1
92.9
100
E30
22.2
2
61.6
114.8
125
230-3-60 16.5
110
25.8
2.8
4.3
10
NONE
-
-
-
37.7
50
E05
5.3
1
12.7
53.7
60
E07
7.5
1
18
60.3
70
E10
10.6
1
25.5
69.6
70
E15
15.9
2
38.2
85.5
90
E20
21.2
2
51
101.5
110
E30
29.6
2
71.2
126.7
150
460-3-60 7.2
52
11.3
2.8
2.1
5
NONE
-
-
-
17.5
20
E07
6.8
1
8.2
27.7
30
E10
10.1
1
12.1
32.7
35
E15
13.6
2
16.4
37.9
40
E20
19.5
2
23.5
46.8
50
E30
28.8
2
34.6
60.8
70
575-3-60 5.5
38.9
8.6
2.8
1.9
4
NONE
-
-
-
13.9
15
E10
10.6
1
10.2
26.6
30
E15
15.9
2
15.3
33
35
E20
21.2
2
20.4
39.4
40
E30
30.4
2
29.3
50.5
60
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
XN036-060 - With Powered Convenience Outlet (Belt Drive) (Continued)
Size
(Tons)
Volt
Compressors
(each)
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Conv
Outlet
Electric Heat Option
MCA
1
(Amps)
Max Fuse
2
/
Breaker
3
Size
(Amps)
RLA LRA MCC
FLA
FLA
FLA
Model
kW
Stages Amps