5188238-YIM-D-0518
Johnson Controls Ducted Systems
39
Table 12: XN Blower Performance Side Duct
XN036 (3 Ton Belt Drive) Side Duct
Air Flow
(CFM)
Available External Static Pressure - IWG
1
1. Blower performance includes 1” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
4. Field Supplied Drive.
0.2
0.4
0.6
0.8
1
1.2
1.4
1.6
1.8
2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Field Supplied Drive
Standard Drive Option
High Static Drive Option
800
678
0.31
761
0.39
840
0.47
917
0.56
991
0.65
1062
0.74
1130
0.84
1195
0.94
1259
1.04
1320
1.16
1000
699
0.37
782
0.44
862
0.51
939
0.60
1012
0.69
1083
0.79
1151
0.88
1217
0.99
1280
1.10
1341
1.20
1200
727
0.40
810
0.47
889
0.56
966
0.64
1040
0.73
1110
0.82
1179
0.93
1244
1.02
1308
1.13
1369
1.23
1400
759
0.46
842
0.53
922
0.61
998
0.69
1072
0.79
1143
0.88
1211
0.98
1276
1.08
1340
1.19
1401
1.30
1600
795
0.56
878
0.63
958
0.70
1035
0.79
1108
0.88
1179
0.98
1247
1.07
1313
1.18
1376
1.28
1438
1.39
FS4
XN048 (4 Ton Belt Drive) Side Duct
Air Flow
(CFM)
Available External Static Pressure - IWG
1
1. Blower performance includes 1” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
4. Field Supplied Drive.
0.2
0.4
0.6
0.8
1
1.2
1.4
1.6
1.8
2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Field Supplied Drive
Standard Drive Option
High Drive
1000
699
0.37
782
0.44
862
0.51
939
0.60
1012
0.69
1083
0.79
1151
0.88
1217
0.99
1280
1.10
1341
1.20
1200
727
0.40
810
0.47
889
0.56
966
0.64
1040
0.73
1110
0.82
1179
0.93
1244
1.02
1308
1.13
1369
1.23
1400
759
0.46
842
0.53
922
0.61
998
0.69
1072
0.79
1143
0.88
1211
0.98
1276
1.08
1340
1.19
1401
1.30
1600
795
0.56
878
0.63
958
0.70
1035
0.79
1108
0.88
1179
0.98
1247
1.07
1313
1.18
1376
1.28
1438
1.39
1800
836
0.68
919
0.76
999
0.84
1075
0.93
1149
1.01
1220
1.11
1288
1.21
1353
1.31
1417
1.41
1478
1.52
2000
880
0.86
963
0.94
1042
1.02
1119
1.11
1193
1.19
1263
1.29
1331
1.39
1397
1.49
1460
1.59
1522
1.70
XN060 (5 Ton Belt Drive) Side Duct
Air Flow
(CFM)
Available External Static Pressure - IWG
1
1. Blower performance includes 1” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
4. Field Supplied Drive.
0.2
0.4
0.6
0.8
1
1.2
1.4
1.6
1.8
2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Field Supplied Drive
Standard Drive Option
High Static Drive
1200
727
0.40
810
0.47
889
0.56
966
0.64
1040
0.73
1110
0.82
1179
0.93
1244
1.02
1308
1.13
1369
1.23
1400
759
0.46
842
0.53
922
0.61
998
0.69
1072
0.79
1143
0.88
1211
0.98
1276
1.08
1340
1.19
1401
1.30
1600
795
0.56
878
0.63
958
0.70
1035
0.79
1108
0.88
1179
0.98
1247
1.07
1313
1.18
1376
1.28
1438
1.39
1800
836
0.68
919
0.76
999
0.84
1075
0.93
1149
1.01
1220
1.11
1288
1.21
1353
1.31
1417
1.41
1478
1.52
2000
880
0.86
963
0.94
1042
1.02
1119
1.11
1193
1.19
1263
1.29
1331
1.39
1397
1.49
1460
1.59
1522
1.70
2200
926
1.08
1009
1.16
1089
1.24
1166
1.33
1239
1.41
1310
1.51
1378
1.61
1444
1.71
1507
1.82
1568
1.92
2400
976
1.35
1059
1.42
1138
1.51
1215
1.59
1289
1.68
1359
1.77
1428
1.88
1493
1.97
1557
2.08
1618
2.19
2600
1028
1.66
1111
1.73
1190
1.80
1267
1.90
1340
1.98
1411
2.08
1479
2.18
1545
2.28
1608
2.39
-