5188238-YIM-D-0518
40
Johnson Controls Ducted Systems
Table 13: XN Blower Performance Bottom Duct
XN036 - 060 (3-5 Ton Direct Drive) Side Duct
UNIT
TONNAGE
MOTOR
1
SPEED
1. Factory set on medium speed tap.
AVAILABLE EXTERNAL STATIC PRESSURE - IWG
2
2. Includes allowances for a wet evaporator coil and 1” filters. Refer to STATIC RESISTANCES Table for resistance values.
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
CFM
W
A
TTS
CFM
W
A
TTS
CFM
W
A
TTS
CFM
W
A
TTS
CFM
W
A
TTS
CFM
W
A
TTS
CFM
W
A
TTS
CFM
W
A
TTS
CFM
W
A
TTS
3
3
3. Side Duct application (230 Volts)
5 (HI)
1528
320
1485
335
1445
349
1409
363
1370
376
1334
390
1292
403
1254
417
1213
430
4 (MED/HI)
1437
263
1391
276
1349
290
1308
303
1265
316
1220
329
1173
343
1119
358
1048
374
3 (MED)
1293
208
1248
221
1205
234
1160
246
1113
258
1065
272
1001
288
934
303
892
313
2 (MED/LOW)
1191
171
1144
183
1096
195
1045
207
991
220
925
235
865
248
-
-
-
-
1 (LOW)
1044
130
963
134
903
145
833
158
-
-
-
-
-
-
-
-
-
-
4
3
5 (HI)
-
-
2007
696
1968
714
1933
734
1896
749
1855
764
1806
769
1719
743
1574
685
4 (MED/HI)
1857
539
1822
557
1786
571
1746
585
1713
602
1671
619
1628
638
1574
657
1500
676
3 (MED)
1672
408
1633
426
1586
438
1550
455
1509
472
1462
490
1408
505
1363
521
1330
536
2 (MED/LOW)
1475
321
1435
335
1388
352
1359
362
1319
376
1271
393
1220
411
1186
422
1142
437
1 (LOW)
1293
223
1252
237
1196
247
-
-
-
-
-
-
-
-
-
-
-
-
5
3
5 (HI)
2245
883
2247
931
2236
950
2211
964
2171
979
2114
971
2034
940
1948
898
1855
854
4 (MED/HI)
2135
771
2116
784
2108
808
2078
826
2041
844
2004
859
1955
861
1886
843
1792
806
3 (MED)
2010
637
1989
656
1975
675
1938
696
1900
715
1867
730
1822
740
1784
756
1716
748
2 (MED/LOW)
1857
539
1822
557
1786
571
1746
585
1713
602
1671
619
1628
638
1574
657
1500
676
1 (LOW)
1293
223
1252
237
1196
247
-
-
-
-
-
-
-
-
-
-
-
-
XN036 (3 Ton Belt Drive) Bottom Duct
Air Flow
(CFM)
Available External Static Pressure - IWG
1
1. Blower performance includes 1” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
0.2
0.4
0.6
0.8
1
1.2
1.4
1.6
1.8
2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Field Supplied Drive
Standard Drive Option
High Static Drive
800
661
0.33
751
0.40
838
0.48
922
0.57
1002
0.65
1079
0.75
1153
0.84
1225
0.94
1294
1.04
1361
1.15
1000
685
0.38
775
0.45
862
0.52
945
0.61
1025
0.69
1103
0.79
1177
0.88
1248
0.98
1317
1.08
1384
1.19
1200
714
0.41
805
0.48
892
0.56
975
0.64
1055
0.73
1132
0.82
1207
0.92
1278
1.02
1347
1.12
1414
1.22
1400
749
0.47
840
0.53
927
0.62
1010
0.70
1090
0.79
1167
0.88
1242
0.98
1313
1.07
1382
1.18
1449
1.29
1600
789
0.56
880
0.63
967
0.70
1050
0.79
1130
0.88
1207
0.97
1282
1.06
1353
1.17
1422
1.26
1489
1.37
FS4
XN048 (4 Ton Belt Drive) Bottom Duct
Air Flow
(CFM)
Available External Static Pressure - IWG
1
1. Blower performance includes 1” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
0.2
0.4
0.6
0.8
1
1.2
1.4
1.6
1.8
2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Field Supplied Drive
Standard Drive Option
High Static Drive
1200
714
0.41
805
0.48
892
0.56
975
0.64
1055
0.73
1132
0.82
1207
0.92
1278
1.02
1347
1.12
1414
1.22
1400
749
0.47
840
0.53
927
0.62
1010
0.70
1090
0.79
1167
0.88
1242
0.98
1313
1.07
1382
1.18
1449
1.29
1600
789
0.56
880
0.63
967
0.70
1050
0.79
1130
0.88
1207
0.97
1282
1.06
1353
1.17
1422
1.26
1489
1.37
1800
833
0.69
924
0.77
1011
0.84
1094
0.93
1174
1.01
1251
1.11
1326
1.20
1397
1.30
1466
1.40
1533
1.51
2000
881
0.86
971
0.94
1058
1.01
1142
1.10
1222
1.19
1299
1.28
1373
1.37
1445
1.48
1514
1.58
1580
1.68
FS4