YPP6830 Pulse Input Rate/Totalizer
Instruction Manual
60
Output 1 and 2 Setup (
OUT 1
,
OUT 2
)
The function of open collector output 1 and 2 is configured using the
Off
,
Pulse
,
Alarm
, and
Timer
menus detailed below.
Pulse Output (
PUlse
)
Pulse outputs may be assigned to rate, total, grand total, retransmit, quadrature, or
test.
Rate Pulse Output (
rate
)
A rate based pulse output is a factor of the rate display and count (output K-factor).
The rate display is a factor of the input pulses, time base, and the input K-factor. The
rate of output pulses over one time base (seconds, minutes, hours, days) is defined
below in terms of input pulses and the input K-factor and count parameters.
For example, if the input K-factor value is set to 10, and the count set to 10, one
output pulse is generated for every 100 input pulses.