YPP6830 Pulse Input Rate/Totalizer
Instruction Manual
25
SETUP AND PROGRAMMING
There is
no need to recalibrate
the meter for frequency in Hz when first received
from the factory.
The meter is
factory calibrated
for Hz prior to shipment. The calibration equip-
ment is certified to NIST standards.
Overview
Setup and programming is done through the infrared Through-Glass buttons, or using
the mechanical buttons when uncovered. There are two slide switches located on the
display module. One is used to configure the input and the other is to lock or unlock
the Through-Glass Buttons.
Through-Glass Buttons
The YPP6830 is equipped with four sensors that operate as through-glass buttons so
that it can be programmed and operated without removing the cover (and exposing
the electronics) in a hazardous area. These buttons can be disabled for security by
using the THRU-GLASS BUTTONS switch and selecting the OFF setting. This switch
is located on the back of the removable electronics module.
Through-Glass Button Operation
To actuate a button, press and remove one finger to the glass directly over the
marked button area. Remove finger to at least 4 inches away from the glass in
between button activations. Through-Glass and mechanical buttons may be held to
cycle through menus or digits in place of repeatedly pushing a button.
Through-Glass Power Save Mode
Through-Glass buttons enter a power saving mode after three minutes of
inactivity. This mode is indicated by a pause symbol (
) appearing in the lower
right of the display. Only the
MENU
button is monitored in this mode. To activate
the Through-Glass buttons, press and hold the menu button for up to five
seconds. The display will read
AWAKE
, and the Through-Glass buttons will be fully
enabled.
Through-Glass Disabled Mode
When the cover is removed, the four mechanical buttons located next to the
sensors may be used. The sensors are disabled when a mechanical button is
pressed and will automatically be re-enabled after 60 seconds of inactivity. The
Through-Glass power symbol (
) will blink in the lower right of the display if the
buttons are disabled due to a mechanical pushbutton being pressed.
!
IMPORTANT
Through-Glass buttons will not work if two or more buttons are
detected as being pressed simultaneously. As a result, be careful
to avoid triggering multiple buttons or reaching across one button