Model YPP6300 Pulse Input Rate/Totalizer
Instruction Manual
39
Programming the Rate/Totalizer (
prog
)
It is
very important
that one reads the following information before
programming the meter:
The meter has been factory calibrated to read input frequency in Hz
(pulses/sec). The calibration equipment is certified to NIST
standards.
Use
the
K-Factor
menu to match the rate/totalizer with a flowmeter’s
k-factor (pulse/unit of measure).
Or
use
the
Scale
menu to scale the pulse input (pulse/sec) without a
signal source.
Or
use
Cal
menu to calibrate the rate/totalizer using a signal source.
The
Program
menu contains the following menus:
1. K-Factor
calibration
2. Scale without a signal source
3. Calibrate with a calibrated signal source
4. Total time base & conversion factor
5. Grand total time base & conversion factor
6. Total reset mode for total & grand total
Note:
The
Scale
and
Calibrate
functions are exclusive of each other.
The meter uses the last function programmed. Only one of these
methods can be employed at a time. The
Scale
and
Calibrate
functions
can use up to 32 points (default is 2). The number of points should be
set in the Advanced menu under the Multi-Point Linearization
(
Linear
)Multi-Point Linearization (
Linear
) menu selection prior to
scaling and calibration of the meter, see page
7676 for details.
The process inputs may be calibrated or scaled to any display value
within the range of the meter.
Grand
Total
Settings
Additional parameters, not needed for most applications, are
programmed in the
Advanced Features
menu; see
Advanced Features
Menu
, page 70.
Summary of Contents for YPP6300
Page 96: ...Model YPP6300 Pulse Input Rate Totalizer Instruction Manual 96...
Page 97: ...Model YPP6300 Pulse Input Rate Totalizer Instruction Manual 97 NOTES...
Page 98: ...Model YPP6300 Pulse Input Rate Totalizer Instruction Manual 98 NOTES...
Page 99: ...Model YPP6300 Pulse Input Rate Totalizer Instruction Manual 99 NOTES...