Model YPP6300 Pulse Input Rate/Totalizer
Instruction Manual
40
K-Factor Calibration (
Factor
)
The meter may be calibrated using the
K-Factor
function. Most flowmeter
manufacturers provide this information with the device. Enter the
K-Factor
(
Factor
) menu and select the decimal point with highest
resolution possible and program the k-factor value (
i.e.
pulses/gal). The
meter will automatically calculate the flow rate using the k-factor and the
time base selected.
ddd.ddd
factor
Factor
prog
d.ddddd
factor
1.8925
6
factor
Multi-Point Calibration & Scaling
The meter is set up at the factory for 2-point linear calibration. The
number of points for multi-point calibration/scaling is set up in the
Advanced
Features
menu. Up to 32 linearization points may be selected.
See page 76 for details.