Model YPP6300 Pulse Input Rate/Totalizer
Instruction Manual
9
SPECIFICATIONS
Except where noted all specifications apply to operation at +25°C.
General
DISPLAY
Main display: 0.6" (15 mm) high, red LEDs
Second display: 0.46" (12 mm) high, red LEDs
6 digits: each (-99999 to 999999), with lead zero blanking.
DISPLAY
INTENSITY
Eight user selectable intensity levels
DISPLAY
UPDATE RATE
Rate: 10 per second; up to 1 per 100 seconds (and is a
function of Low Gate setting)
Total: 10 per second (fixed)
OVERRANGE
Display flashes
999999
DISPLAY
ASSIGNMENT
The main (Big) and small (Little) displays may be assigned
to rate, total, grand total, alternate rate & total, max/min,
units (small display only), set points, and Modbus input.
PROGRAMMING
METHODS
Four front panel buttons, digital inputs, PC and
PRO
PLUS
software, Modbus registers, or cloning using Copy function.
RECALIBRATION
All ranges are calibrated at the factory to read frequency in
Hz. No recalibration required.
MAX/MIN
DISPLAY
Max/min readings reached by the process are stored until
reset by the user or until power to the meter is turned off.
PASSWORD
Three programmable passwords restrict modification of
programmed settings and two prevent resetting the totals.
Pass 1: Allows use of function keys and digital inputs
Pass 2: Allows use of function keys, digital inputs and editing set/reset points
Pass 3: Restricts all programming, function keys, and digital inputs.
Total: Prevents resetting the total manually
Gtotal: Prevents resetting the grand total manually
NON-VOLATILE
MEMORY
All programmed settings are stored in non-volatile memory
for a minimum of ten years if power is lost.
POWER
OPTIONS
85-265 VAC 50/60 Hz, 90-265 VDC, 20 W max
or jumper selectable 12/24 VDC
10%, 15 W max
FUSE
Required external fuse: UL Recognized, 5 A max, slow
blow; up to 6 meters may share one 5 A fuse
ISOLATED
TRANSMITTER
POWER SUPPLY
Terminals P+ & P-: 24 VDC
10% @ 200 mA max (standard),
(12/24 VDC powered models rated @ 100 mA max).
5 or 10 VDC @ 50 mA max, selectable with internal jumper J4.
ISOLATION
4 kV input/output-to-power line
500 V input-to-output or output-to-P+ supply
Summary of Contents for YPP6300
Page 96: ...Model YPP6300 Pulse Input Rate Totalizer Instruction Manual 96...
Page 97: ...Model YPP6300 Pulse Input Rate Totalizer Instruction Manual 97 NOTES...
Page 98: ...Model YPP6300 Pulse Input Rate Totalizer Instruction Manual 98 NOTES...
Page 99: ...Model YPP6300 Pulse Input Rate Totalizer Instruction Manual 99 NOTES...