background image

Yokogawa Electric Corporation - TC10 - ENGINEERING MANUAL - PAG. 1

TC10

TEMPERATURE 

CONTROLLER

Engineering Manual

Code: IM 05C01E81-02EN 

Third edition: 

Feb.

 201

8

Yokogawa Electric Corporation

2-9-32 Nakacho, Musashino-shi, Tokyo 180-8750 Japan

www.yokogawa.com/ns

1.  OUTLINE DIMENSIONS (mm)

1.1  INSTRUMENT DIMENSIONS

48

48

48

PV

AT

14

11

8 mm max.

Optional

gasket 

1.2  PANEL CUT-OUT

65 mm min.

2.56 in min.

45

+0.6

 mm

1.78

+0.023

 in

45

+0.6

 mm

1.78

+0.023

 in

65 mm min. 2.56 in min.

1.3  MOUNTING REQUIREMENTS

This instrument is intended for permanent installation, for 
indoor use only, in an electrical panel which encloses the 
rear housing, exposed terminals and wiring on the back.
Select a mounting location having the following characteristics:

1. 

It should be easily accessible;

2. 

There is minimum vibrations and no impact;

3. 

There are no corrosive gases;

4. 

There are no water or other fluids (i.e. condensation);

5. 

The ambient temperature is in accordance with the 
operative temperature (0 to 50°C);

6. 

The relative humidity is in accordance with the instrument 
specifications (20 to 90%);

The instrument can be mounted on panel with a maximum 
thickness of 8 mm.
When the maximum front protection (IP65) is desired, the 
optional gasket must be mounted.

2.  CONNECTION DIAGRAM

D -

D +

+

+

+

+

+

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

Out1

Out3

Out2

C

NO

+

-

C

NO

+

-

C

NO

+

-

DI1

Out4

DI2

Power

supply

RS485

12 VDC/20 mA max.

Relay Out 1: 

4 (4) A/250 VAC

Relay Out 2, 3:   2 (1) A/250 VAC

SSR Out 1, 2 , 3: 10 VDC/15 mA

SSR Out4: 

12 VDC/20 mA

Current Out1: 

0/4 to 20 mA, 0/2 to 10V

Passive TX, 2 wires, 4 to 20 mA

Pt1000

Pt100

TC

4 to 20 mA (active)

0/12 to 60 mV

, 0/1 to 5V

, 0/2 to 10

V

-

+

-

2.1  GENERAL NOTES ABOUT WIRING

1. 

Do not run input wires together with power cables.

2. 

External components (like zener barriers, etc.) connected 
between sensor and input terminals may cause errors in 
measurement due to excessive and/or not balanced line 
resistance or possible leakage currents.

3. 

When a shielded cable is used, it should be connected at 
one point only.

4. 

Pay attention to the line resistance; a high line resistance 
may cause measurement errors.

Summary of Contents for TC10

Page 1: ...ce with the operative temperature 0 to 50 C 6 The relative humidity is in accordance with the instrument specifications 20 to 90 The instrument can be mounted on panel with a maximum thickness of 8 mm...

Page 2: ...mpedance 1 M for mV Input 500 k for Volt Input 2 2 5 mA Input 0 4 to 20 mA input wiring for passive transmitter using the auxiliary pws _ 4 to 20 mA Passive transmitter 4 1 Input impedance 53 Internal...

Page 3: ...1 OP1 Relay Output C NO 7 8 Contact rating 4 A 250 V cosj 1 2 A 250 V cosj 0 4 Operation 1 x 105 SSR Output SSR 7 8 Logic level 0 Vout 0 5 VDC Logic level 1 12 V 20 15 mA max Current Analog Output mA...

Page 4: ...l gasket is mounted for indoor locations according to EN 60070 1 Terminals protection IP 20 according to EN 60070 1 Installation Panel mounting Terminal block 16 screw terminals for cables of 0 25 to...

Page 5: ...or ON OFF or Heat Cool control with 1 alarm V N N DC Output for SSR V R R DC Output for SSR with 2 alarm relays or DCV and relay output for Heat Cool control with 1 alarm V V R 2 DCV outputs for SSR w...

Page 6: ...figuration parameters The complete configuration method allows to take advantage of all instrument features giving more capabilities it requires more actions and time Note that you can take advantage...

Page 7: ...on The upper display shows cod2 flashing while the lower display shows 0000 or the cod2 value stored in memory 6 Using and buttons set the code 2 value according to the following tables P Q R S Prepar...

Page 8: ...o return to the previous group Proceed as follows Push the button and maintaining the pressure then push the button release both the buttons Note The group selection is cyclic as well as the selection...

Page 9: ...n an underrange is detected the po wer output will be forced to the value of 8 oPE parameter 8 oPE Safety output value Available Always Range 100 to 100 of the output Notes 1 When the instrument is pr...

Page 10: ...When a Sequential set point selection is used diF1 or diF2 18 every closure of of the logic input increase the value of SPAT active set point of one step The selection is cyclic SP SP2 SP3 SP4 12 di...

Page 11: ...Heating output see warning c rEG Cooling output AL Alarm output t out Reserved t HoF Reserved P End Reserved P HLd Reserved P uit Reserved P run Reserved P Et1 Reserved P Et2 Reserved or bo Out of ran...

Page 12: ...ute band alarm with alarm indication inside the band SE br Sensor break LodE Deviation low alarm relative HidE Deviation high alarm relative LHdo Relative band alarm with alarm indication out of the b...

Page 13: ...e difference between the Alarm threshold value and the point the Alarm automatically resets 2 When the alarm threshold plus or minus the hysteresis is out of input range the instrument will not be abl...

Page 14: ...le When 36 AL2t different from nonE Range 0 Never 1 During stand by 2 During overrange and underrange 3 During overrange underrange and stand by AL3 Group Alarm 3 parameters 44 AL3t Alarm 3 type Avail...

Page 15: ...ID 52 LbAt LBA time Available When 56 Cont PID Range oFF LBA not used 1 to 9999 seconds 53 LbSt Delta measure used by LBA during Soft start Available When 52 LbAt is different from oFF Range oFF loop...

Page 16: ...ed for all process subjected to big load variation able to change heavily the process response Available When 56 cont PID Range YES self tune active no self tune not active 60 HSEt Hysteresis of the O...

Page 17: ...and soft start function are programmed the instrument performs the soft start and than the program function 4 The auto tune function will be performed after soft start function 5 The Soft start functi...

Page 18: ...ill be used as remote set point Note A 84 SPrt change produces the following actions When 84 SP rt rSP the remote set point will be forced to be equal to the active set point When 84 SP rt trin the re...

Page 19: ...t Display time out Available Always Range oFF The display is ever ON 0 1 to 99 59 minutes and seconds Note This function allows to turn OFF the display when no alarm is present and no action is made o...

Page 20: ...e threshold set with parameter 137 h Job the display shows r iSP Inspection Requested The count reset with r iSP cancellation can be done only by changing the threshold value parameter 137 h Job Using...

Page 21: ...is NOT password protected Notes 1 The limited access parameter are collected in a list 2 The sequence of the limited access parameters is programmable and can be made according to your needs 3 The par...

Page 22: ...1 when the instrument is powered it starts immediately to work according to the memorized parameter value In other words the instrument has one status only the run time status During run time we can f...

Page 23: ...ocedures Allows to start the Direct set point modification fun ction see below Allows to display the additional informations see below 7 4 2 Direct set point modification This function allows to modif...

Page 24: ...lute alarms are operative or not according to the ALxo Alarm x enabling during Stand by mode parameter setting 2 If you set stand by mode during program execution the program will be aborted 3 If you...

Page 25: ...sponsibility for any damage to people things or animals deriving from violation wrong or improper use or in any case not in compliance with the instrument s features 9 2 WARRANTY This product is under...

Page 26: ...s 1 0 7 inE Sensor error used to enable the safety output value or Over range ou Under range our Over and under range our 8 oPE Safety output value of the output 100 to 100 0 9 IO4 F I O 4 function on...

Page 27: ...d the programmed threshold 15 Ao1L Initial scale value of the analog retransmission when Out 1 is an analog output dP 1999 Ao1H 1999 16 Ao1H Full scale value of the analog retransmission when Out 1 is...

Page 28: ...days counter has reached the programmed threshold AL 23 o3AL Alarms linked up with the out 3 0 0 to 63 1 Alarm 1 2 Alarm 2 4 Alarm 3 8 Loop break alarm 16 Sensor Break 32 Overload on output 4 AL2 24 o...

Page 29: ...abled in stand by mode 2 Alarm 1 enabled in out of range condition 3 Alarm 1 enabled in stand by mode and in overrange condition 0 AL2 group no Param Description Dec Point Values Default 36 AL2t Alarm...

Page 30: ...3 enabled in stand by mode and in overrange condition 0 LBA group Loop Break Alarm Parameters no Param Description Dec Point Values Default 52 LbAt LBA time 0 From 0 oFF to 9999 s oFF 53 LbSt Delta m...

Page 31: ...0 100 to 100 0 74 SSt Soft start time 2 0 00 oFF 0 01 to 7 59 hh mm inF always ON oFF 75 SS tH Threshold for soft start disabling dP 1999 to 9999 E U 9999 SP group Set point parameters no Param Descri...

Page 32: ...d Reserved P t tu Reserved P t td Reserved ti uP Reserved ti du Reserved PErc Percent of the power output used during soft start when the soft start time is equal to infinite the limit is ever active...

Page 33: ...e controller is forced in stand by when Co ty value reaches the threshold set in 137 h Job 8 Totalizer of control relay worked days number of hours the con trol relay has been in ON condition divided...

Page 34: ...Yokogawa Electric Corporation TC10 ENGINEERING MANUAL PAG 34...

Page 35: ...Yokogawa Electric Corporation TC10 ENGINEERING MANUAL PAG 35...

Page 36: ...Yokogawa Electric Corporation TC10 ENGINEERING MANUAL PAG 36...

Reviews: