7-5
IM 04P03B01-01E
Specifications
7
Printouts (Pen Model)
Item
Specifications
Recording pen (color)
Plotter pen (purple)
Alarm printout
Prints alarm occurrence/release.
Printout contents
Occurrence (
)/release (
) marks, channel No. or tag, alarm type, alarm level, time, printout
buffer overflow mark.
Time printout format
Selectable from hour:minute, hour:minute:second, month:day:hour:minute,
month:day:hour:minute:second, and year:month:day:hour:minute:second.
Alarm printout buffer
Stores 8 occurrences of alarm information waiting to be printed.
Periodic printout
Prints at specified time intervals from the reference time.
Interval
Reference time: 00 hour 00 minute to 23 hour 00 minute (1 hour steps, minute fixed)
(see appendix 1)
Auto:
Automatically determined from the chart speed.
Manual: Select 10 min, 12 min, 15 min, 20 min, 30 min, 1 hour, 2 hours, 3 hours, 4 hours, 6 hours,
8 hours, 12 hours, or 24 hours.
Mode
Select no periodic printout or print instantaneous values.
Printout contents
Date/Time, offset compensation ON/OFF, channel information (measured value, alarm status, unit,
delta computation ON/OFF, scale, channel number or tag, recording color), chart speed (with time
ticks)
Message printout
Prints preset message strings.
Number of messages
5
Printout contents
Time, message (up to 16 characters), printout buffer overflow mark.
Time printout format
Selectable from hour:minute, hour:minute:second, month:day:hour:minute,
month:day:hour:minute:second, year:month:day:hour:minute:second, and not print.
Message printout buffer
Stores 5 messages waiting to be printed.
Recording start printout
Prints at the start of recording.
Printout contents
Time and chart speed, printout buffer overflow mark.
Time printout format
Selectable from hour:minute, hour:minute:second, month:day:hour:minute,
month:day:hour:minute:second, and year:month:day:hour:minute:second.
New chart speed printout
Prints when the chart speed is changed.
Printout contents
Chart speed and time, printout buffer overflow mark.
Time printout format
Selectable from hour:minute, hour:minute:second, month:day:hour:minute,
month:day:hour:minute:second, and year:month:day:hour:minute:second.
Manual printout
Prints the measured values of all channels.
Printout contents
Measured values of all channels at that point.
Trend recording is temporarily suspended.
Setting printout (List)
Prints the settings of items in Setting mode.
Printout contents
Range setting, alarm setting, etc.
Trend recording is temporarily suspended.
Setting printout (setup list) Prints the settings of items in Basic Setting mode.
Printout contents
Basic alarm specifications, basic recording specifications, etc.
Trend recording is temporarily suspended.
Items dependent on the chart speed
10 to 1500 mm/h
1800 mm/h or higher
Periodic printout
Alarm printout
Message printout
Recording start printout
New chart speed printout
Chart speed
Printed
Not printed
10 to 15 mm/h
20 to 30 mm/h
40 to 60 mm/h
75 to 120 mm/h
150 to 180 mm/h
200 to 300 mm/h
360 to 1500 mm/h
Periodic printout interval
8 hours
4 hours
2 hours
1 hour
30 minutes
20 minutes
10 minutes
Chart speed
Date printout format
Select the printout format of the date from Y/M/D, M/D/Y, D/M/Y, D.M.Y, and M.D.Y. The format
applies to the date printout of all printout items .
7.3 Recording Function Specifications