6-6
IM 04P03B01-01E
Explanation
Zero position (
): Left edge of the chart paper
Full position (
): Right edge of the chart paper
to
:
Pen number 1 to 4
Adjustment
Zero position: 00 to 70, full position: –45 to 15
A value change of 1 corresponds to 0.033 mm change in the pen position. Decreasing
the value moves the pen to the left and increasing the value moves the pen to the right.
Note
The procedure is different when the customized menu is enabled.
•
When “P-ADJ” of the customized menu is ON
Carry out steps 1 to 4 in “Adjusting the Pen Position.”
Select “FREE” and press the
key to display “P-ADJ.”
Carry out the steps beginning with 5 in “Adjusting the Pen Position.”
•
When “P-ADJ” of the customized menu is OFF
See “Releasing the Customized Menu” or “Changing the Settings without Releasing the
Basic Setting Mode Lock.”
<Related Topics>
Releasing the customized menu: Section 4.21
Changing the settings without releasing the basic setting mode lock:
Section 4.21
6.4 Adjusting the Pen Position (Pen Model)