2-3
IM 04P03B01-01E
Frequently Used Setup Operations (Setting Mode)
2
1-5V Input
(RANGE)
(CH1)
(1-5V)
(ON)
(OK)
Select “1-5V.”
Select the channel number.
Set the left span value.
Set the right span value.
Select the right scale value.
The settings are activated.
Select “RANGE.”
Channel number
Span left
Decimal point
Span right
Scale left
Scale right
Low-cut
(When low-cut is enabled)
Select whether to use low-cut.
Select the left scale value and the decimal place.
Description
• Span Left and Span Right
Selectable span left range: 0.8 to 1.2 V
Selectable span right range: 4.8 to 5.2 V
• Scale Left, Scale Right, and Decimal Place
Selectable range (mantissa): –19999 to 30000
Example: The value in the range of –100.00 to 350.00 cannot be specified. The
mantissa of scale right is 35000, which exceeds the upper limit to 30000.
Set in the range of –100.0 to 350.0.
Decimal place: XXXXX, XXXX.X, XXX.XX, XX.XXX, X.XXXX
To set the decimal place for the left scale setup item, press the
key to make
blink, then press the
or
key.
The decimal position is the position specified by scale left.
Make sure that left scale is less than scale right.
• Low-Cut
ON (
):
Cuts values less than or equal to 0% of the recording span (sets
such values to 0% (scale left value)).
OFF (
):
Does not apply the low-cut function.
<Related Topics>
Setting the unit: Section 2.3
Enabling the low-cut function: Section 4.15
2.1 Setting the Input Range