n
Grounding of grounding bar for shield lines
The N-IO field enclosure has a grounding bar for shield lines to connect shield lines of signal
cables in an enclosure. At the time of delivery, this grounding bar for shield lines is internally
connected to a grounding bar in the enclosure.It is possible to separate the protective grounding
system of the grounding bar for shield lines from the one of the enclosure system by changing
the grounding connection as shown in the figure below.
SEE
ALSO
See “Section 3.3.2 Connecting grounding cable to grounding bar for shield lines”, for the cables and terminals.
Protective grounding system
Protective grounding system
F010303.ai
Protective conductor terminal
Grounding cable
Grounding cable
Grounding bar for sheild lines
Grounding bar
Cable entry
Figure Grounding of grounding bar for shield lines