2. Transportation, storage and installation
2-7
TI 30A30A10-01EN
2.5
Installing equipment
This section describes the precautions required to install the N-IO field enclosure.
n
Precautions for installing the enclosure
• The mounting surface shall be flat and vertical and the mounting support shall be capable of
withstanding a load of approx. 4 times the product weight or more.
• When installing the enclosure on concrete, use proper concrete anchor screws.
• When installing the enclosure on a steel plate, drill holes and use M10 lock washers and
nuts to secure it.
• Provide a heat dissipation space (g) of at least 100 mm over the top of the enclosure.
In addition, provide a space (h) under the enclosure, which includes a cable bending radius
space for cables passed through the cable entry at the bottom (provide the proper space to
suit the cables used).
• Do not put any object on the top surface of the enclosure.
F020501.ai
Front view
g
h
Figure Space over and under the enclosure
Feb. 26, 2018-00