3. Cabling
3-2
TI 30A30A10-01EN
3.2
Connecting power cable
n
Power cables
Nominal conductor cross-section area: AWG10 (5.5 mm
2
equivalent) or more
Temperature rating of cables: Enclosure ambient tempe 35 ºC or more
Note: Use cables capable of supplying current required by respective pieces of equipment with low voltage drop.
Note: Ensure to secure the minimum bending radius of the cable. The minimum bending radius is either the value shown in the cable
manufacturer’s specifications or six-fold of the cable conductor diameter, whichever is bigger should be applied.
n
Power cable termination
l
Solderless (crimp-on) lug terminal processing
Use solderless lugs for power cables (see Figure). Use solderless (crimp-on) terminals with
insulating cover, which have low contact resistance little aging.
F030201.ai
Insulation covering
inside diameter
Hole diameter
Lug outside
diameter
Lug length
Figure Solderless (crimp-on) lug
l
Solderless (crimp-on) lug specifications
The solderless lug to use must have the dimensions given in table according to the nominal cross
sectional area of the power cable for which the lug is to be used.
Crimping terminal: For round crimping terminal M5
Table Solderless lug dimensions
Nominal cross
sectional area
(mm
2
)
Screw used
(mm)
Hole diameter
(mm)
Lug outside
diameter
(mm)
Lug length
(mm)
Insulation
covering inside
diameter
(mm)
5.5
5 (*1)
5.3 or more
9.7 or less
approx.29
5.9 or more
*1:
Recommended tightening torque: 2.5 Nm to 3.0 Nm
CAUTION
• Always use solderless lugs with insulating covering.
• Always use solderless lugs and crimp-on tool manufactured by the same manufacturer.
• The crimp-on tool must be matched to the wire thickness.
Feb. 26, 2018-00