3. Cabling
3-8
TI 30A30A10-01EN
n
Signal cables
Nominal conductor cross-sectional area:
0.5 to 2.5 mm
2
(AWG 20 to 14)
Temperature rating of cables: Enclosure ambient tempe 35 ºC or more
Note: Ensure to secure the minimum bending radius of the cable. The minimum bending radius is either the value shown in the cable
manufacturer’s specifications or six-fold of the cable conductor diameter, whichever is bigger should be applied.
n
Signal cable termination
Connect the cable either with the cable coating stripped (without a sleeve) or with a sleeve
attached.
When using a sleeve
At the cable end, peel off the coating and attach a sleeve. The specifications of the sleeve differ,
depending on the cable thickness. Provide cable termination according to the following figure and
tables:
L1
L2
L1
Sleeve with insulating cover
Core
Cable
Peel-off length
F030501.ai
Sleeve (without insulating cover)
Figure Cable termination
Table When sleeves with insulating cover are used
Nominal cross
sectional area (mm
2
)
Peel-off length
(mm)
Sleeve dimensions (mm)
Weidmuller model
No.
L1
L2
0.5
10
14
8
H0.5/14
0.75
10
14
8
H0.75/14
1.0
10
14
8
H1.0/14
1.5
10
14
8
H1.5/14
2.5
11
14
8
H2.5/14D
Table When sleeves without insulating cover are used
Nominal cross
sectional area (mm
2
)
Peel-off length
(mm)
Sleeve dimensions (mm)
Weidmuller model
No.
L1
0.5
6
6
H0.5/6
0.75
6
6
H0.75/6
1.0
6
6
H1.0/6
1.5
7
7
H1.5/7
2.5
7
7
H2.5/7
When not using a sleeve
The peel-off length should be 7 mm.