10. General Specifications
>
10-2
IM 01W03D01-01EN
Diagnosis Functions:
Power failures, inter module communication
failures, sensor communication failures,
memory errors, battery alarm, abnormal
temperature
Software Download Function:
Software download function permits to update
wireless field device software via ISA100
Wireless communication.
INSTALLATION ENVIRONMENT
Ambient Temperature Limits:
Operating: -40 to 85°C (altitude up to 3000 m)
-30 to 80°C (LCD visible range)
Storage: -40 to 85°C
Ambient Humidity Limits:
Operating: 0 to 100%RH (non-condensation)
Storage: 0 to 100%RH (non-condensation)
Ambient Temperature Gradient:
Operating: ±10°C/h or less
Storage: ±20°C/h or less
Vibration Resistance:
0.21 mm P-P (10 - 60 Hz), 3 G (60 - 2 kHz)
Shock Resistance:
50 G 11 ms
REGULATORY COMPLIANCE
STATEMENTS
This product satisfies the following standards.
* Please confirm that an installation region fulfills an
applicable standard. If additional regulatory information
and approvals are required, contact a Yokogawa
representative.
CE Conformity:
EMC Directive:
EN61326-1 Class A Table 2, EN55011 Class A
RoHS Directive:
EN50581
ATEX Directive:
See “OPTIONAL SPECIFICATIONS (For
Explosion Protected Types)”
Other Normative Standards:
Safety: EN61010-1 (Indoor/Outdoor use)
Canadian Safety Standards:
CAN/CSA-C22.2 No.61010-1
CAN/CSA-C22.2 No.94.1,
CAN/CSA-C22.2 No.94.2
IEC 60529
Degrees of Protection:
IP66, IP67 and Type 4X apply when the
connector is properly tightened.
PHYSICAL SPECIFICATIONS
Connections:
Refer to “MODEL AND SUFFIX CODES”.
Housing Material:
Plastic (Polycarbonate)
Weight:
500 g (without mounting bracket, clamp, and
battery)
Mounting:
Refer to “MODEL AND SUFFIX CODES”.