<2. Handling Cautions>
2-18
IM 01W03D01-01EN
WARNING / AVERTISSEMENT
• DANGER POTENTIEL DE CHARGES
ÉLECTROSTATIQUES
- QUAND LE MATÉRIEL EST
UTILISÉ DANS DES ENDROITS
DANGEREUX, ÉVITER TOUTE
ACTION QUI GENERENT CHARGES
ELECTROSTATIQUES, COMME
FROTTANT AVEC UN CHIFFON SEC
• QUAND LE MATÉRIEL EST UTILISÉ DANS
LA ZONE 0, IL DOIT ÊTRE INSTALLÉE TELLE
QUE, MÊME EN CAS D’INCIDENTS RARE,
SOURCES D’ALLUMAGE DUE AUX IMPACTS
ET SPARKS FRICTION EST EXCLUE
• POUR ÉVITER ALLUMAGE DES
ATMOSPHÉRES INFLAMMABLES OU
COMBUSTIBLES, LISEZ, COMPRENDRE
ET RESPECTER ELS PROCÉDURES
D’ENTRETIEN DU CONSTRUCTEUR
• UTILISER UNIQUEMENT DES
ACCUMULATEUR F9090FC OU F9090GC
(YOKOGAWA)
• LA BATTERIE PEUT ÊTRE REMPLACÉ
DANS DES ENDROITS DANGEREUX.
BATTERIE POSSÈDE UNE RÉSISTANCE
DE SURFACE QUI EST SUPÉRIEURE À 1
G OHM ET DOIT ÊTRE INSTALLÉ DANS
L’ENVELOPPE DE L’ÉQUIPEMENT, SOIN
PENDANT LE TRANSPORT ET DEPUIS LE
POINT DE L’INSTALLATION POUR ÉVITER
CHARGE ÉLECTROSTATIQUE BUILD-UP
• CELLULES DOIVENT ÊTRE CHANGÉ
DANS UN ENDROIT UNCLASSIFIED
SEULEMENT
• SUBSTITUTION DE COMPOSANTS PEUT
IMPAIR LA SÉCURITÉ INTRINSÈQUE
• Be sure to use the specified battery pack
and batteries. For details, refer to section 8.5
“Handling Batteries.”
• With an intrinsically safe Products, the
battery pack is replaceable in a hazardous
area. During the replacement work, make
sure that dust and water droplets do not
enter inside the products. For details on how
to replace the battery pack, refer to section
8.3 “Replacing the Battery Pack.”
2.6.3 ATEX Certification
(1) Technical Data
Caution for ATEX Intrinsically safe type.
Note 1. Model FN310 Field Wireless Multi-Protocol
Module (HART Protocol) with optional code
/KS27 for potentially
explosive atmospheres:
• No. FM15ATEX0069X
• Applicable Standards:
EN 60079-0:2012+A11:2013,
EN 60079-11:2012,
EN 60079-28:2015
• Type of Protection and Marking code:
Ex ia op is IIC T4 Ga
• Group: II
• Category: 1 G
• Amb. Temp.: –40 to 70°C (–40 to 158°F)
• Enclosure: IP66 according to
EN 60529:1991+A1:2000+A2:2013
Note 2. Electrical Parameters
(Refer to the Control Drawing)
Note 3. Installation
• Installation should be in accordance with
local installation requirements.
(Refer to the Control Drawing)
[Control Drawing, IFM043-A72 for ATEX
Certification]
• One-to-one Connection [2-wire or 4-wire
(Passive)]
4
5
3
2
1
1
2
3
4
Wireless
Communication
Connector
Terminal
VOUT
Not used
Ui
≥
Uo
Ii
≥
Io
Pi
≥
Po
Ci
≤
Co- Ccable
Li
≤
Lo- Lcable
Ui
≥
Uo
Ii
≥
Io
Pi
≥
Po
Ci, Li: See*
1
Wireless Communication
(Connector)
VOUT
(Terminal 1, 2)
FN310
Field Wireless Multi-Protocol
Module(HART)
Intrinsically Safe
Apparatus (1)
Intrinsically Safe Apparatus (2)
or
Associated Apparatus (2)
Not used
Hazardous Area
Hazardous Area
or
Non-Hazardous Area
F0216.ai
Uo :
5.88 V
Io :
613 mA
Po :
907 mW
Co :
5.82 µF
Lo :
25 µH
Uo :
23.1 V
Io :
87 mA
Po :
450 mW
Co :
100 nF
Lo :
3
mH