<9. Parameter Summary>
9-10
IM 01W03D01-01EN
Table 9.2
Diagnostic Status Detail
Bit
Diagnostic Status Detail
Description
Diagnostic
status
assignment bit
NAMUR
NE107
Category
*
Diagnostic Status Detail.1
31
ADAPTER FAIL
FN310 failure
Bit27
F
30
ANTENNA FAIL
FN110 failure
Bit27
F
28
INTERNAL BUS FAIL
Communication failure between FN110 and
FN310
Bit27
F
27
SENSOR FAIL
Disconnection or communication error,
between the HART device and FN310
Bit26
F
15
DEVICE CONNECTION ERR
Connection error between the HART device
and FN310
Bit25
C
14
DEVICE ADDRESS ERR
Address error of the HART device
Bit25
C
13
BURST MODE
Detect a Burst Mode of the HART device
Bit25
C
12
BOOT TIME ERR
Boot Time setting error of the HART device
Bit25
C
9
LOWBAT_ALM
Low remaining battery voltage
Bit19
M
8
CRITICAL LOWBAT
Low remaining battery voltage
Bit20
M
7
ADAPTER TEMP HI
FN310 temperature is above +85°C
Bit22
O
6
ADAPTER TEMP LO
FN310 temperature is below -40°C
Bit22
O
5
ANTENNA TEMP HI
FN110 temperature is above +85°C
Bit22
O
4
ANTENNA TEMP LO
FN310 temperature is below -40°C
Bit22
O
Diagnostic Status Detail.2
31
AI1 OUT OF SERVICE
AI1 O/S Mode
Bit24
C
30
AI2 OUT OF SERVICE
AI2 O/S Mode
Bit24
C
29
AI3 OUT OF SERVICE
AI3 O/S Mode
Bit24
C
28
AI4 OUT OF SERVICE
AI4 O/S Mode
Bit24
C
15
AI1 SIMULATION ACTIVE
AI1 Simulate Mode
Bit17
C
14
AI2 SIMULATION ACTIVE
AI2 Simulate Mode
Bit17
C
13
AI3 SIMULATION ACTIVE
AI3 Simulate Mode
Bit17
C
12
AI4 SIMULATION ACTIVE
AI4 Simulate Mode
Bit17
C
Diagnostic Status Detail.3
31
HART DEVICE
MALFUNCTIONED
Detect HART Status Device Malfunctioned
Bit8
F
30
HART DEVICE
CONFIGURATION CHANGED
Detect HART Status Configuration Changed
Bit7
C
29
HART DEVICE COLD START
Detect HART Status Cold Start
Bit7
C
28
HART DEVICE MORE STATUS
AVAILABLE
Detect HART Status More Status Available
Bit7
C
27
HART DEVICE LOOP CURRENT
FIXED
Detect HART Status Loop Current Fixed
Bit7
C
26
HART DEVICE LOOP CURRENT
SATURATED
Detect HART Status Loop Current Saturated
Bit6
O
25
HART DEVICE NON PRIMARY
VARIABLE OOL
Detect HART Status Non Primary Variable
out of limits
Bit6
O
24
HART DEVICE PRIMARY
VARIABLE OOL
Detect HART Status Primary Variable out of
limits
Bit6
O
*: NAMUR NE 107 “Self-Monitoring and Diagnosis of Field Devices”