<7. Setting Parameters>
7-13
IM 01W03D01-01EN
Table 7.6
Diagnostic Results Summary
Diagnostic Status
Contents
Alert
Type
NAMUR
NE107
Category*
Diagnostic Status Detail
Description
Faults in electronics
78
F
ADAPTER FAIL
FN310 failure
ANTENNA FAIL
FN110 failure
INTERNAL BUS FAIL
Communication failure between FN110
and FN310
Faults in sensor or
actuator element
77
F
SENSOR FAIL
Communication failure between FN310
and HART devices
Installation,
calibration problem
76
C
DEVICE CONNECTION ERR
Connection failure between FN310 and
HART devices
DEVICE ADDRESS ERR
Address setting error of HART devices
BURST MODE
Burst mode detection of HART devices
BOOT TIME ERR
Boot time setting error of HART devices
Out of service
75
C
AI1 OUT OF SERVICE
AI1 O/S Mode
AI2 OUT OF SERVICE
AI2 O/S Mode
AI3 OUT OF SERVICE
AI3 O/S Mode
AI4 OUT OF SERVICE
AI4 O/S Mode
Environmental
conditions out of
device specification
73
O
ADAPTER TEMP HI
FN310 temperature is above +85°C
ADAPTER TEMP LO
FN310 temperature is below -40°C
ANTENNA TEMP HI
FN110 temperature is above +85°C
ANTENNA TEMP LO
FN110 temperature is below -40°C
Power is critical low:
maintenance need
short-term
71
M
CRITICAL LOWBAT
Low battery alert
Power is low:
maintenance need
mid-term
70
M
LOWBAT_ALM
Low battery
Simulation is active
68
C
AI1 SIMULATION ACTIVE
AI1 Simulation Mode
AI2 SIMULATION ACTIVE
AI2 Simulation Mode
AI3 SIMULATION ACTIVE
AI3 Simulation Mode
AI4 SIMULATION ACTIVE
AI4 Simulation Mode
Connected device:
Failure
59
F
HART DEVICE
MALFUNCTIONED
Detect HART Status Device
Malfunctioned
Connected device:
Function Check
58
C
HART DEVICE
CONFIGURATION CHANGED
Detect HART Status Configuration
Changed
HART DEVICE COLD START
Detect HART Status Cold Start
HART DEVICE MORE STATUS
AVAILABLE
Detect HART Status More Status
Available
HART DEVICE LOOP CURRENT
FIXED
Detect HART Status Loop Current
Fixed
Connected device:
Out of Specification
57
O
HART DEVICE LOOP CURRENT
SATURATED
Detect HART Status Loop Current
Saturated
HART DEVICE NON PRIMARY
VARIABLE OOL
Detect HART Status Non Primary
Variable out of limits
HART DEVICE PRIMARY
VARIABLE OOL
Detect HART Status Primary Variable
out of limits
*: NAMUR NE107 “Self-Monitoring and Diagnosis of Field Devices”