<9. Parameter Summary>
9-2
IM 01W03D01-01EN
Object
ID
Attribute
ID
Label
Description
Default value
Handling
*1
1.
UAPMO
block
(continued)
102
Diagnostic
Status Detail
Detailed information on Diagnostic Status.
Refer to Table
9.2
W
103
Energy Left
Indicates the number of days of remaining battery
life assuming ambient temperature condition as 23
degrees Celsius.
Unit: day
---
R
104
Reset Energy
Left
Resets the remaining battery power calculation to
restore it to a remaining battery power calculation
which is based on new batteries.
0: Continue
1: Reset
0 (reading
value is always
0)
W(P)
105
Power Supply
Status
Indicates remaining battery life and power supply of
device.
0: line powered
1: battery powered, greater than 75%
remaining capacity
2: battery powered, between 25% and 75%
remaining capacity
3: battery powered, less than 25% remaining
capacity
---
R
106
Energy Harvest
Type
Available to write note into this parameter.
---
W(P)
107
Power Supply
Voltage
Indicates the measured power supply voltage (V).
---
R
110
Hardware Write
Protect
Indicates the status of the hardware write protection
switch.
0: Off
1: On
---
R
111
Antenna
Temperature
Indicates the temperature of the FN110.
---
R
112
Adapter
Temperature
Indicates the temperature of the FN310.
---
R
113
Temperature
Unit
Selects the temperature unit to be indicated on
Antenna Temperature and Adapter Temperature.
1000: K
1001: °C (default)
1002: °F
1003: °R
°C
W(P)
131
Connected
Device
Maintenance
Alert
The On/Off or priority for Connected Device
Maintenance Alert can be set.
1. On/Off setting
0: On, 255: Off (default)
2. Alert report priority: 0 to 15 (default: 15)
1. Off
2. 15
W(P)
132
Connected
Device Function
Check Alert
The On/Off or priority for Connected Device
Function Check Alert can be set.
1. On/Off setting
0: On, 255: Off (default)
2. Alert report priority: 0 to 15 (default: 15)
1. Off
2. 15
W(P)
133
Connected
Device Out Of
Specification
Alert
The On/Off or priority for Connected Device Out Of
Specification Alert can be set.
1. On/Off setting
0: On, 255: Off (default)
2. Alert report priority: 0 to 15 (default: 15)
1. Off
2. 15
W(P)
134
Connected
Device Failure
Alert
The On/Off or priority for Connected Device Failure
Alert can be set.
1. On/Off setting
0: On, 255: Off (default)
2. Alert report priority: 0 to 15 (default: 15)
1. Off
2. 15
W(P)