<9. Parameter Summary>
9-7
IM 01W03D01-01EN
Object
ID
Attribute
ID
Label
Description
Default value
Handling
*1
8.
IFO
block
(continued)
112
PV Damping
Indicates the PV Damping in seconds fields
contained in the HART Command 15.
0
R
113
PV Flags
Indicates the PV Flags fields contained in the HART
Command 15.
0
R
114
Write Protect
Indicates the Write Protection Flag fields contained
in the HART Command 15.
0
R
115
Distributor Code Indicates the Private Label Distributor Code fields
contained in the HART Command 0 response.
0
R
117
Transmitter
Status Alert
Mask
The device status to detect when Transmitter
Status has changed can be set. When enabled,
it sends an Alert when it detects the state of the
target. It is disabled by setting the Bit each of the
following.
Bit7: Device Malfunction
Bit6: Configuration Changed
Bit5: Cold Start
Bit4: More Status Available
Bit3: Loop Current Fixed
Bit2: Loop Current Saturated
Bit1: Non-Primary Variable Out of Limits
Bit0: Primary Variable Out of Limits
0x28
W(P)
118
Transmitter
Message
Indicates the Message fields contained in the HART
command 12 response. This is converted according
to the Table 7.2.
---
R
128
Power Source
Select the method of supplying power to the HART
device.
0: Battery (default)
1: Line Powered
Battery
W(P)
129
Boot Strap Time Set the time until the HART device can acquire
the process value stable after starts up. When the
Boot Strap Time is longer than the Publish period,
in order to supply continuous power to the HART
device, battery life will be shorter.
Unit: second
Range: 1 to 3500
5
W(P)
130
Configuration
Saving Time
Set the time until the HART device save the setting
after change settings.
Unit: second
Range: 0 to 300
30
W(P)
141
HART Master
Mode
Select the Master Mode of FN310
1: Primary (default)
0: Secondary
Primary
W(P)
142
HART Preamble Set the number of the Preamble to be added to the
top of the HART frame when starting to transmit the
HART Command by FN310.
Range: 0 to 20
5
W(P)
143
HART Retry
Count
Indicates the integrated value of the number of
retries when HART communication error has
occurred.
3
R