<7. Setting Parameters>
7-7
IM 01W03D01-01EN
7.3.3 Parameters for Wireless
Communication
(1) Network Information
Concentrator Object block: Configuration
The network-related information can be checked.
(2) Update Time
CO block: Data publication period
Set the update time value to 5 to 3600 seconds.
The setting affects the battery life.
When update time is set 0 second, FN310 stops
updating process variables via the field wireless
network. And it also stops the acquisition of process
variables from the HART device.
(3) Remaining Battery Life
UAPMO block: Energy Left
The number of days of battery life remaining is
indicated assuming ambient temperature condition
as 23 °C. It takes several days for the value to be
stabilized after the power on and initialization of the
remaining battery life.
UAPMO block: Reset Energy Left
When changing batteries, the remaining battery life
is initialized by Reset Energy Left parameter.
(4) LCD Display
TRANSDUCER block: LCD Intermittent Time
The integral indicator has three modes: Continuous,
Intermittent, and Off. These modes are switched by
LCD Intermittent Time parameter. The intermittent
mode repeats on/off at defined seconds.
In any mode, current process value is displayed by
magnet switch operation. After displaying current
process value, returns to the configured mode.
Refer to subsection 8.6 “Switching LCD Display” for
details.
NOTE
When the FN310 detects AL.01, AL.02 and
AL.03 error, the LCD display does not dim
regardless of the status in LCD mode. See Table
8.4 for details.
7.3.4 Tag and Device Information
You can specify the Device Tag when ordering
the corresponding FN110 Field Wireless
Communication Module.
Device Tag and device information can be checked
as follows.
Procedure to Read the Device Tag and Device
Information
• Device Tag (Software Tag)
This is specified by writing characters (up to
16 characters) that differs from those specified
in Tag No. to the module. For details how to
confirm this, refer to subsection “Connecting to
the Field Wireless Network”.
• Tag Description
This is a universal parameter to store the
comment that describes the content of the tag
located in the TRANSDUCER and AI1/AI2/AI3/
AI4 blocks.
Limitation of Device Information
When changing the device information, input the
information based on the following limitation on the
number of characters.
• Message function (up to 32 characters)
TRANSDUCER block: Tag Description
AI1/AI2/AI3/AI4 block: Tag Description
7.3.5 Setup the Integral Indicator
TRANSDUCER block: LCD Exp Mode
Set the display method of the PV on the integral
indicator. Index display or base display is
selectable.