5-21
IM CW500-01EN
Example of Swell and Inrush Current Detection
For details, see “Displaying Recorded Events” (section 6.7).
Rms value (1)
Rms value (2)
Rms value (3) Rms value (5) Rms value (7) Rms value (9)
Rms value (4) Rms value (6) Rms value (8)
Voltage/current
waveform
Rms waveform
Hysteresis
Threshold
(4)
(5)
(6)
(7)
(8)
(9)
(1)
(2) (3)
Dip (Instantaneous voltage drop)
Set the dip threshold (rms voltage in one cycle) as a percentage of the
nominal voltage. The selectable range varies depending on the VT ratio.
Hysteresis is applied to this threshold.
Settings
0 to 100 % (90 %*) of the nominal voltage
* Default value
<Procedure>
Use the up and down arrow keys to move to DIP.
→
Press ENTER to
show a value entry window.*
→
Use the arrow keys to enter a percentage
of the nominal voltage.
* The input range is shown in a pop-up.
5.3 Measurement Setup