8-4
IM CW500-01EN
Output Terminals
Output terminals transmit low level signals while a power quality event is
occurring. The terminals are normally at high level. If the event lasts less
than 1 second, the output signal is set to low level for 1 second.
The output target event is the event with the highest priority among
the specified events. If you want the output to synchronize with a lower
priority event, turn off events that are higher priority than that event. For
details, see “Power Quality (Event) Threshold Settings” in page 5-18. The
events are arranged in order by priority below.
[Highest priority]
→
Transient
→
Interruption
→
Dip
→
Swell
→
Inrush current
+5V
H
L
OUTPUT
Output format: Open collector output
Maximum input: 30 V, 50 mA, 200 mW
Output voltage: Hi 4 to 5 V
Lo 0 to 1 V
8.2 Signal Control with External Devices