YMGI
•
Your Modern Green Idea
35
TROUBLESHOOTING
POSSIBLE CAUSES
SOLUTIONS
UNIT DOES NOT START
Unit may have become unplugged
Fuse may have blown
Circuit breaker may have been tripped
Unit may be off or in 24V thermostat control mode.
Check section on Advanced Settings to verify set
properly.
Unit may be in a protection or diagnostic failure
mode. See section on ERROR codes.
Check that plug is plugged securely in wall receptacle.
Note
: Plug has a test/reset button on it. Make sure that
the plug has not tripped.
Replace the fuse.
Reset circuit breaker.
Turn unit on.
DISPLAY HAS STRANGE NUMBERS / CHARACTERS
ON IT
The unit may be in a diagnostic mode. Check diagnostic
codes--- checking Control section to determine if the unit
has had a failure.
The unit may be set for °C (instead of °F). See the
Advanced Settings
to change.
UNIT MAKING NOISES
•
Clicking, gurgling and whooshing noises are normal
during operation of unit.
UNIT NOT COOLING / HEATING ROOM
•
Unit air discharge section is blocked
•
Temperature setting is not high or low enough
•
Note: Set point limits may not allow the unit to
heat or cool the room to the temperature desired.
Check the section on Advanced Settings
•
Unit air filters are dirty.
•
Room is excessively hot or cold when unit is
started
•
Vent door left open
•
Unit may be in a protection or diagnostic failure
mode. Check section on Intelligent Self ---
checking Control.
•
Compressor is in time delay. There is a protective
time delay (approx. 3 minutes) on starting the
compressor after a power outage (or restarting
after it has been turned off), to prevent tripping of
the compressor overload.
•
Make sure that curtains, blinds or furniture are not
restricting or blocking unit airflow.
•
Reset to a lower or higher temperature setting.
•
Remove and clean filters.
•
Allow sufficient amount of time for unit to heat or cool the
room.
•
Start heating or cooling early before outdoor temperature,
cooking heat or gatherings of people make room
uncomfortable.
•
Close vent door.
•
Wait approximately 3- minutes for compressor to start
WATER DRIPPING OUTSIDE
•
If a drain kit has not been installed, condensation runoff
during very hot and humid weather is normal. See Note 2.
If a drain kit has been installed and is connected to a
drain system, check gaskets and fittings around drain for
leaks and plugs.
WATER DRIPPING INSIDE
Wall sleeve is not installed level
Wall sleeve must be installed level for proper drainage of
condensation. Check that installation is level and make
any necessary adjustments.
ICE OR FROST FORMS ON INDOOR COIL
•
Low outdoor temperature
•
Dirty filters
•
When outdoor temperature is approximately 55 °F
(12.8°C) or below, frost may form on the indoor coil unit
when the unit is in Cooling mode. Switch unit to FAN
operation until ice or frost melts.
•
Remove and clean filters.
COMPRESSOR PROTECTION
•
Power may have cycled, so compressor is in a
restart protection.
•
Random Compressor restart
: Whenever the unit is
plugged in, or power has been restarted, a random
compressor restart will occur. After a power outage, the
compressor will restart after approximately 3 minutes.
•
Compressor Protection
: To prevent short cycling of the
compressor, there is a random startup delay of 3 minutes
and a minimum compressor run time of 3 minutes.
NOTES
:
1.
If circuit breaker is tripped or fuse is blown more than once, contact a qualified electrician.
2.
If unit is installed where condensation drainage could drip in an undesirable location, an accessory drain kit should be installed and
connected to drain system.
Summary of Contents for TTWA Series
Page 10: ...YMGI Your Modern Green Idea 10...
Page 27: ...YMGI Your Modern Green Idea 27 OPERATING INSTRUCTIONS...
Page 37: ...YMGI Your Modern Green Idea 37 TTWA Wiring Diagrams TTWA0 Wiring Diagram AC Only...
Page 38: ...YMGI Your Modern Green Idea 38 TTWA0 Wiring Diagram AC Heater...
Page 39: ...YMGI Your Modern Green Idea 39 TTWA0 Wiring Diagram HP...
Page 40: ...YMGI Your Modern Green Idea 40 TTWA0 Wiring Diagram HP Heater...