ERROR CODES
Error code
Content of defect
E2
Room temperature sensor loose or broken
E3
Indoor coil temperature sensor loose or broken
E4
1. Air outlet temperature sensor loose or broken
2. Air outlet over heating fault in Electric Heat Mode
E5
Outdoor coil temperature sensor loose or broken
E8
Defrosting in Cool Mode or over heating protection in Heat pump Mode
E9
High pressure protection in Cool Mode
SOLUTIONS:
For E2, E3, E5, chec
k the sensors’ plug, make sure that they are inserted firmly. Or replace the related
sensor.
E4
Follow the 3 steps for repairing:
1. Check whether there is any obstacle in front of the unit that block the room return air flow, if so,
remove the obstacle.
2. Check the indoor fan, make sure it is running properly, if not, repair the fan.
3. Check the related sensor plug, make sure that it is inserted firmly, or replace the sensor.
E8
-If the ambient temperature is too high to run heat pump mode, or it is too low to run cooling mode, it may
cause the E8 error. Otherwise, follow the same steps as E4 to solve the issue.
E9
-If the outdoor ambient temperature is too high to run cooling mode, it may cause the E9 error, otherwise,
follow the 3 steps for repairing:
1. Check whether there is any obstacle blocks the outdoor unit air flow, if so, remove the obstacle.
2. Check the outdoor fan, make sure it is running properly, if not, repair the fan.
3. Check the outdoor coil sensor plug, make sure that it is inserted firmly. Or replace the sensor.
Summary of Contents for TTWA Series
Page 10: ...YMGI Your Modern Green Idea 10...
Page 27: ...YMGI Your Modern Green Idea 27 OPERATING INSTRUCTIONS...
Page 37: ...YMGI Your Modern Green Idea 37 TTWA Wiring Diagrams TTWA0 Wiring Diagram AC Only...
Page 38: ...YMGI Your Modern Green Idea 38 TTWA0 Wiring Diagram AC Heater...
Page 39: ...YMGI Your Modern Green Idea 39 TTWA0 Wiring Diagram HP...
Page 40: ...YMGI Your Modern Green Idea 40 TTWA0 Wiring Diagram HP Heater...