Monitor Constants
6-
91
Selecting Pulse Monitor Items
Output digital operator monitor items (U1-
[status monitor]) from pulse monitor terminal MP-AC. Refer
to
Chapter 5
User Constants
, and set the
part of U1-
(Status monitor). The possible monitor selec-
tions are limited as follows: U1-01, 02, 05, 20, 24, 36.
Adjusting the Pulse Monitor Items
Adjust the pulse frequency output from pulse monitor terminal MP-AC. Set the pulse frequency output when
100% frequency is output to H6-07.
Set H6-06 to 2, and H6-07 to 0, to output the frequency synchronous with the Inverter's U-phase output.
Application Precautions
When using a pulse monitor constant, connect a peripheral device according to the following load conditions.
If the load conditions are different, there is a risk of characteristic insufficiency or damage to the machinery.
Using a Sourcing Output
Output Voltage
(Isolated)
VRL (V)
Load Impedance (k
Ω
)
+5 V min.
1.5 k
Ω
min.
+8 V min.
3.5 k
Ω
min.
+10 V min.
10 k
Ω
min.
Load impedance
MP
AC
VRL
Using a Sinking Input
External Power
Supply (V)
12 VDC
±
10%,
15 VDC
±
10%
Sink Current (mA)
16 mA Max
Load impedance
Sinking c
u
rrent
External po
w
er s
u
pply
MP
AC