* The factory settings in the parentheses are for 3-wire sequence.
Multi-function Contact Input Functions
H1-10
Terminal S12
function selec-
tion
Multi-function contact input
10
0 to 79
15
No
A
A
A
A
A
409H
-
端子 S12 设定
Set-
ting
Value
Function
Control Methods
Page
V/f
V/f
with
PG
Open
Loop
Vec-
tor
1
Flux
Vec-
tor
Open
Loop
Vec-
tor
2
0
3-wire sequence (Forward/Reverse Run Command)
Yes
Yes
Yes
Yes
Yes
6-11
1
Local/Remote selection (ON: Local, OFF: Remote)
Yes
Yes
Yes
Yes
Yes
6-76
2
Option/Inverter selection (ON: Option board)
Yes
Yes
Yes
Yes
Yes
6-83
6-164
3
Multi-step speed reference 1
When H3-05 is set to 0, this function is combined with the master/auxiliary speed
switch.
Yes
Yes
Yes
Yes
Yes
6-5
4
Multi-step speed reference 2
Yes
Yes
Yes
Yes
Yes
6-5
5
Multi-step speed reference 3
Yes
Yes
Yes
Yes
Yes
6-5
6
Jog frequency command (higher priority than multi-step speed reference)
Yes
Yes
Yes
Yes
Yes
6-5
7
Accel/decel time 1
Yes
Yes
Yes
Yes
Yes
6-19
8
External baseblock NO (NO contact: Baseblock at ON)
Yes
Yes
Yes
Yes
Yes
6-77
9
External baseblock NC (NC contact: Baseblock at OFF)
Yes
Yes
Yes
Yes
Yes
6-77
A
Acceleration/deceleration ramp hold (ON: Acceleration/deceleration stopped, fre-
quency on hold)
Yes
Yes
Yes
Yes
Yes
6-78
B
OH2 alarm signal input (ON: OH2 will be displayed)
Yes
Yes
Yes
Yes
Yes
-
C
Multi-function analog input selection (ON: Enable)
Yes
Yes
Yes
Yes
Yes
-
D
No V/f control with PG (ON: Speed feedback control disabled,) (normal V/f con-
trol)
No
Yes
No
No
No
6-137
E
Speed control integral reset (ON: Integral control disabled)
No
Yes
No
Yes
Yes
6-137
F
Not used (Set when a terminal is not used)
-
-
-
-
-
-
10
Up command (Always set with the down command)
Yes
Yes
Yes
Yes
Yes
6-79
11
Down command (Always set with the up command)
Yes
Yes
Yes
Yes
Yes
6-79
12
FJOG command (ON: Forward run at jog frequency d1-17)
Yes
Yes
Yes
Yes
Yes
6-84
13
RJOG command (ON: Reverse run at jog frequency d1-17)
Yes
Yes
Yes
Yes
Yes
6-84
14
Fault reset (Reset when turned ON)
Yes
Yes
Yes
Yes
Yes
7-2
15
Emergency stop. (Normally open condition: Deceleration to stop in deceleration
time set in C1-09 when ON.)
Yes
Yes
Yes
Yes
Yes
6-17
16
Motor switch command (Motor 2 selection)
Yes
Yes
Yes
Yes
Yes
-
17
Emergency stop (Normally closed condition: Deceleration to stop in deceleration
time set in C1-09 when OFF)
Yes
Yes
Yes
Yes
Yes
6-17
18
Timer function input (Functions are set in b4-01 and b4-02 and the timer function
outputs are set in H1-
and H2-
.)
Yes
Yes
Yes
Yes
Yes
6-105
19
PID control disable (ON: PID control disabled)
Yes
Yes
Yes
Yes
Yes
6-109
Con-
stant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO-
BUS
Regis-
ter
Page
Display
V/f
V/f
with
PG
Open
Loop
Vec-
tor
1
Flux
Vec-
tor
Open
Loop
Vec-
tor
2