6
-42
Machine Protection
This section explains functions for protecting the machine.
Reducing Noise and Leakage Current
The switching frequency of the Inverter’s output transistor can be changed to reduce carrier noise and leakage
current from the motor.
Related Constants
* 1. The factory settings depend on the capacity of the Inverter. The values for a 200 V Class Inverter for 0.4 kW are given.
* 2. The setting ranges depend on the capacity of the Inverter. The values for a 200 V Class Inverter for 0.4 kW are given.
* 3. This constant can be monitored or set only when F is set for C6-02.
* 4. Displayed in Quick Programming Mode when motor 2 is set for a multi-function input.
* 5. The maximum output frequency depends on the setting for the carrier frequency (refer to page 6-43).
Con-
stant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO
BUS
Regis-
ter
Display
V/f
V/f
with
PG
Open
Loop
Vector
1
Flux
Vec-
tor
Open
Loop
Vec-
tor
2
C6-02
Carrier fre-
quency
selection
Select carrier wave fixed pattern.
Select F to enable detailed settings using
constants C6-03 to C6-07.
1 to F
*2
6
*1
No
Q
Q
Q
Q
No
*4
224H
载波频率选
择
C6-03
*3
Carrier
frequency
upper limit
Set the carrier frequency upper limit and
lower limit in kHz units.
The carrier frequency gain is set as fol-
lows:
With the vector control method, the
upper limit of the carrier frequency is
fixed in C6-03.
K is a coefficient that depends on the
setting of C6-03.
C6-03
≥
10.0 kHz: K = 3
10.0 kHz > C6-03
≥
5.0 kHz: K = 2
5.0 kHz > C6-03: K = 1
2.0 to
15.0
*2 *5
15.0
kHz
*1
No
A
A
A
A
No
225H
载波频率上
限
C6-04
*3
Carrier
frequency
lower limit
0.4 to
15.0
*2 *5
15.0
kHz
*1
No
A
A
No
No
No
226H
载波频率下
限
C6-05
*3
Carrier fre-
quency
propor-
tional gain
00 to
99
00
No
A
A
No
No
No
227H
载波频率比
例增益
C6-11
Carrier fre-
quency
selection
for open-
loop vector
2 control
Select the carrier frequency when open-
loop vector 2 control is used.
1: 2 kHz
2: 4 kHz
3: 6 kHz
4: 8 kHz
1 to 4
1
*1
No
No
*4
No
*4
No
*4
No
*4
Q
22DH
无 PG 矢量 2
载波
Carrier frequency
Output frequency x (C6-05) x K
(Max. output frequency)
Output
frequency