
7 Troubleshooting
YASKAWA Europe
TOMP_C710606_75A V1000 IP66 - Quick Start Guide
EN 25
Operator Programming Errors
An Operator Programming Error (OPE) occurs when an inapplicable parameter is set or an individual parameter setting is inappropriate. When an
OPE error is displayed, press the ENTER button to display U1-18 (OPE fault constant). This monitor will display the parameter that is causing the
OPE error.
Input Phase Loss
• Input voltage drop or phase imbalance.
• One of the input phase is lost.
• Loose wires at the drive input.
• Check the power supply.
• Make sure that all cables are properly fixed to the correct terminals.
Braking Transistor
Fault
The internal braking transistor is broken.
• Cycle the power supply.
• Replace the drive if the fault reoccurs.
DC Undervoltage
The voltage in the DC bus fell below the undervoltage detection level
(L2-05).
• The power supply failed or one input phase has been lost.
• The power supply is too weak.
• Check the power supply.
• Make sure, that the power supply is strong enough.
Controller
Undervoltage
The drives controller power supply voltage is too low.
• Cycle power to the drive. Check if the fault reoccurs.
• Replace the drive if the fault continues to occur.
DC Charge Circuit
Fault
The charge circuit for the DC bus is broken.
• Cycle power to the drive. Check if the fault reoccurs.
• Replace the drive if the fault reoccurs.
<1> Please contact YASKAWA to replace internal or external cooling fan in case of Heatsink Overheat Alarm
LED Operator
Display
Cause
Corrective Action
oPE01
Drive capacity and value set to o2-04 do not match.
Correct the value set to o2-04.
oPE02
Parameters were set outside the allowable setting range.
Set parameters to the proper values.
oPE03
A contradictory setting is assigned to multi-function contact inputs
H1-01 through to H1-06.
• The same function is assigned to two inputs. (this excludes
“External fault” and “Not used”)
• Input functions which require the setting of other input functions
were set alone.
• Input functions that are not allowed to be used simultaneously
have been set.
• Fix any incorrect settings.
• Refer to the Technical Manual for more details.
oPE05
• The run command source (b1-02) or frequency reference source
(b1-01) is set to 3 but no option board is installed.
• The frequency reference source is set to pulse input but H6-01 is
not 0.
• Install the required option board.
• Correct the values set to b1-01 and b1-02.
oPE07
Settings to multi-function analog inputs H3-02 and H3-10 and PID
functions conflict.
• H3-02 and H3-10 are set to the same value. (this excludes settings
“0” and “F”)
• PID functions have been assigned to both analog inputs and the
pulse input at the same time.
• Fix any incorrect setting.
• Refer to the Technical Manual for more details.
oPE08
A function has been set that cannot be used in the control mode
selected. (might appear after control mode change)
• Fix any incorrect setting.
• Refer to the Technical Manual for more details.
oPE10
The V/f pattern setting is incorrect.
• Check the V/f pattern settings.
• Refer to the Technical Manual for more details.
LED Display
ALM FLT
Cause
Corrective Action
TOMP_C710606_75A_0_0_prePrint.pdf 57
21.12.2010 13:52:25