2 Mechanical Installation
EN 10
YASKAWA Europe
TOMP_C710606_75A V1000 IP66 - Quick Start Guide
2.
Route the cables through the cable glands, following the instructions in
Cable Glands on page 10
.
3.
Tighten the cable gland caps.
4.
Connect the power supply cable to the EMC Filter. Use only the green colored screws for grounding. Connect motor cable to inverter main
terminals and control circuit to the control terminals.
5.
Install option cards if required. For drives CIMR-VCBA
HAA-00
and CIMR-VC4A0001HAA-00
to CIMR-VC4A0011HAA-
00
place the bottom cover and terminal cover delivered with the drive before attaching the option card.
Reattaching the Front Cover
NOTICE:
Be careful not to pinch or damage the front cover sealing when attaching the front cover. Any damage to the sealing may allow moisture or oil to enter the drive
case and damage components.
NOTICE:
Equipment Hazard. Be sure to fastening all screws in accordance with specified tightening torque. If any screws are loose, water and oil may seep into the case
and damage the drive.
1.
For drives with digital operator in the front cover insert the LED operator cable back into the correct port on the drive.
2.
Place the front cover back onto the drive, and fasten the cover screws applying the following tightening torque values:
Drives CIMR-VCBA
and CIMR-VC4A0001 to 0011: 1.5 Nm
Drives CIMR-VC4A0018 to 0038: 2.5 Nm
Cable Glands
NOTICE:
Equipment Hazard. Use only the recommended multiconductor cable and use one cable per cable gland only. Attempting to pass more than one wire through a
cable gland will result in a space between those wires, thus considerably reducing the water-proofing and dust-proofing capabilities of the cable gland, and may
result in damaging the drive.
NOTICE:
Make sure that the rubber edging along the outside of the cable gland is properly sealed. Failing to properly seal the outside may allow water or oil into the drive
and damage components.
Cable Glands Specifications and Model Numbers
YASKAWA recommends using SKINTOP cable glands by Lapp Kabel for use with V1000 Series IP66 Type.
Cable
Cable Gland
(Cap)
EMC Filter
Terminals
grounding
of cable shield