44
YASKAWA
TOEPC71061782C GA800 Drive Installation & Primary Operation
Figure 10.2 Tightening Torque Display Location (Reverse side of Front Cover)
Figure 10.3 Tightening Torque Display Location (Lower Front Side of Front Cover)
■
Control Circuit Wire Gauges and Tightening Torques
Use the tables in this section to select the correct wires. Use shielded wire to wire the control circuit terminal block.
Use crimp ferrules on the wire ends to make the wiring procedure easier and more reliable.
Table 10.6 Control Circuit Wire Gauges and Tightening Torques
Terminal Block
Terminal
Screw Size
Tightening
Torque
N
∙
m (lbf
∙
in)
Bare Wire
Crimp Ferrule
Recomm.
Gauge
mm
2
(AWG)
Applicable
Gauge
mm
2
(AWG)
Recomm.
Gauge
mm
2
(AWG)
Applicable
Gauge
mm
2
(AWG)
TB1
S1 - S8, SN, SC, SP
M3
0.5 - 0.6
(4.4 - 5.3)
0.75
(18)
•
Stranded wire
0.2 - 1.0
(24 - 16)
•
Solid wire
0.2 - 1.5
(24 - 16)
0.5
(20)
0.25 - 0.5
(24 - 20)
TB2
M1 - M6, MA, MB, MC
TB3
+V, AC, -V, A1, A2, A3, FM, AM,
AC, MP, RP, AC
TB4
E (G), SN, HC, H1, H2, PS, AC, D
+, D-
TB5
E (G)
M3.5
0.5 - 1.0
(4.4 - 8.9)
0.5 - 2
(20 - 14)
1.25
(12)
-
-
Crimp Ferrules
Attach an insulated sleeve when you use crimp ferrules. Refer to
for the recommended external
dimensions and model numbers of crimp ferrules.
Use the CRIMPFOX 6, a crimping tool made by PHOENIX CONTACT.