48
YASKAWA
TOEPC71061782C GA800 Drive Installation & Primary Operation
Figure 10.11 Locations of Switches
Table 10.8 I/O Terminals and Switches Functions
Position
Switch
Terminal
Function
Default
A
DIP switch S2
-
Enables and disables the MEMOBUS/Modbus communications
termination resistor.
OFF
B
Jumper Switch S5
FM, AM
Sets terminals FM and AM to voltage or current output.
FM: V (voltage output)
AM: V (voltage output)
C
DIP switch S1-1
A1
Sets the input signal type (voltage/current).
V (voltage input)
DIP switch S1-2
A2
Sets the input signal type (voltage/current).
I (current input)
DIP switch S1-3
A3
Sets the input signal type (voltage/current).
V (voltage input)
D
DIP switch S4
A3
Sets MFAI or PTC input.
AI (analog input)
◆
Control I/O Connections
This section gives information about the settings for the listed control circuit I/O signals.
•
MFDI (terminals S1 to S8)
•
Pulse train output (terminal MP)
•
MFAI (terminals A1 to A3)
•
PTC input (terminal A3)
•
MFAO (terminals FM, AM)
•
MEMOBUS/Modbus communications (terminals D+, D-, AC)
■
Pulse Train Output
You can use pulse train monitor output terminal MP for sourcing mode or for sinking mode.
•
Use for sourcing mode
The load impedance changes the voltage level of the pulse train output signal.
Load Impedance
R
L
(k
Ω
)
Output Voltage
V
MP
(V)
1.5 kΩ or more
5 V or more
4.0 kΩ or more
8 V or more
10 kΩ or more
10 V or more
Note:
Use the formula in
to calculate the necessary load resistance (kΩ) to increase output voltage V
MP
(V).