14
YASKAWA
TOEPC71061782C GA800 Drive Installation & Primary Operation
■
Ambient Temperature Setting
Maintain the ambient temperature within the following ranges according to the enclosure type.
•
IP00/UL Open Type: -10 °C to +50 °C (14 °F to 122 °F)
•
IP55/UL Type 12 Heatsink External Mounting; front side: -10°C to +50 °C (14 °F to 122 °F)
•
IP55/UL Type 12 Heatsink External Mounting; back side: -10°C to +40 °C (14 °F to 104 °F)
6
Mechanical Installation
This section gives information about the standard environment for correct installation.
◆
Drive Exterior and Mounting Dimensions (IP00/UL Open Type)
For additional IP00/UL Open Type drive dimension information, refer to the Technical Reference manual (document
number SIEPC71061737).
For IP55/UL Type 12 Heatsink External Mounting dimension information, refer to the Installation Manual (document
number TOEPC71061779) and the Quick Setup Procedures (document numbers TOEPC71061780 and
TOEPC71061781).
For dimensions and installation instructions for other external heatsink installations, refer to the External Heatsink
Installation Kit Instruction Manual (document number TOEPC72060003).
For product weights, refer to the drive nameplate.
Table 6.1 IP00/UL Open Type Exterior and Mounting Dimensions for Models T103 to T168
Model
Dimensions mm (in)
W
H
D
W1
W2
H1
H2
d
T103
255
(10.04)
450
(17.72)
280
(11.02)
170
(6.69)
165
(6.50)
424
(16.69)
16
(0.63)
M6
T140 - T168
264
(10.39)
543
(21.38)
335
(13.19)
190
(7.48)
182
(7.17)
516
(20.31)
17.5
(0.69)
M8