Installation and Operation Guide SOLECTRIA
®
XGI 1500-250 Series Inverters
DOCR-071074 (Rev 7, 30 MAY 2023)
62 of 72
88% <= V < 110%
No trip
No trip
110% <= V <= 120%
1.0 s
13 s
f > 120%
0.16 s
0.16 s
Table 10-5 Frequency Limits and Trip Times
Frequency Range (± 0.05 Hz)
Clearing Time (± 0.2 s)
Clearing Time Adjustable Up to
and Including (± 0.1 s)
F < 57 Hz
0.16 s
10 s
57 Hz <= F < 59.5 Hz
2.0 s
300 s
59.5 Hz <= F < 60.5 Hz
No trip
No trip
60.5 Hz <= F <= 62 Hz
2.0 s
300 s
V > 62 Hz
0.16 s
10 s
Figure 10-1 Derating with AC Voltage