Installation and Operation Guide SOLECTRIA
®
XGI 1500-250 Series Inverters
DOCR-071074 (Rev 7, 30 MAY 2023)
61 of 72
Measurement Accuracy
Table 10-2 Accuracy Specifications
Enclosure
Table 10-3 Enclosure Information
Enclosure Finish, Rating
Polyester Powder-Coated Aluminum, NEMA 4X, IEC IP66, Type 3R
Dimensions
Height: 29.5 in. (750 mm)
Width: 44.3 in. (1125 mm)
Depth: 15.4 in. (390 mm)
Weight
290 lbs (131.5 kg)
Mounting Angle Range
Vertical Only
Voltage and Frequency Limits and Trip Times
All models of the SOLECTRIA XGI 1500-250 series inverters comply with UL1741 Edition 3 (09/28/2021),
IEEE 1547.1 2020, and IEEE 1547-2018 requirements. The SOLECTRIA XGI 1500-250 series inverters
comply with IEEE 1547-2018 Normal Operating Performance Category B, and with Abnormal Operating
Performance Category III.
The tables below show its standard settings.
Table 10-4 Default Voltage Limits and Trip Times
Voltage Range (± 1%)
Clearing Time (± 0.2 s)
Clearing Time Adjustable Up to
and Including (± 0.1 s)
V < 45%
0.16 s
0.16 s
45% <= V < 60%
1.0 s
11 s
60% <= V < 88%
2.0 s
21 s